Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC90-150 www.goodmanmfg.com 5
prodUCt speCifiCations — 10 tons
CPC120
XXX3BXXX
CPC120
XXX4BXXX
CPC120
XXX7BXXX

Total BTU/h 118,000 118,000 118,000
Sensible BTU/h 87,300 87,300 87,300
EER / IEER 11.5 / 11.2 11.5 / 11.2 11.5 / 11.2
Decibels 83.0 83.0 83.0
ARI Reference #s 3023833 3023833 3023833

Motor Type Belt Drive Belt Drive Belt Drive
Indoor Nominal CFM 4,000 4,000 4,000
Indoor motor FLA (Cooling) 7.8 3.9 2.7
Horsepower - RPM 2.0/1725 2.0/1725 2.0/1725
Piston Size (Cooling) 0.086 0.086 0.086
Filter Size (Qty) (4) 16” x 24” x 2” (4) 16” x 24” x 2” (4) 16” x 24” x 2”
Drain Size (NPT) ¾” ¾” ¾”
R-410A Refrigerant Charge Cir #1 & #2 220 oz. 220 oz. 220 oz.
Evaporator Coil Face Area (²) 10.2 10.2 10.2
Rows Deep / Fins per Inch 4 / 14 4 / 14 4 / 14

# of Wheels (D x W) (1) 15” x 15” (1) 15” x 15” (1) 15” x 15”
Motor Sheave / Blower Sheave VL40 / AK74 VL40 / AK74 VL40 / AK74
Belt AX51 AX51 AX51

Quanty of Condenser Fan Motors 2 2 2
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3
Outdoor Nominal CFM 7,200 7,200 7,200
Face Area (²) 32.4 32.4 32.4
Rows Deep - Fins per Inch 2/2 rows - 22 fpi 2/2 rows - 22 fpi 2/2 rows - 22 fpi

Quanty / Type 2 / Scroll 2 / Scroll 2 / Scroll
Stage 1 1 1

Voltage/Phase/ Frequency 208-230/3/60 460/3/60 575/3/60
Quanty of Compressors 2 2 2
Compressor RLA / LRA ea. 16/110.0 7.8/52.0 5.7/38.9
Standard Max Stac 2.0” 2.0” 2.0”
Outdoor Fan RLA ea. 2.40 1.20 0.89
Total Unit Amps 45 22 16
Min. Circuit Ampacity¹ 49 24 17
Max. Overcurrent Protecon (amps)² 60.0 30 20
Entrance Power Supply
Locang
Dimple
Locang
Dimple
Locang
Dimple
Entrance Control Voltage
 1135 1135 1135
 1175 1175 1175
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.