Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC90-150 www.goodmanmfg.com 13
heat kit eleCtriCal data (Blower only, heat mode) — 8½ tons
kw CorreCtion faCtors

 240 230 220 210 208
 1 0.93 0.82 0.78 0.76

 460 440 430
 0.92 0.84 0.8
For other voltage, use voltage² / 480²

 560 550 540
 0.95 0.91 0.88
Multiply rated kW by correction factor to get actual kW.


MCA¹











CPC102XXX3BXXX 43 50
EHK3-16 55 60 15 3400 - 3825 CFM 3400 - 3825 CFM
EHK3-30 100 100 30 3400 - 3825 CFM 3400 - 3825 CFM
EHK3-45 139 150 43 3400 - 3825 CFM 3400 - 3825 CFM


MCA¹











CPC102XXX4BXXX 20 25
EHK4-16 27 30 15 3400 - 3825 CFM 3400 - 3825 CFM
EHK4-30 50 50 30 3400 - 3825 CFM 3400 - 3825 CFM
EHK4-45 70 70 43 3400 - 3825 CFM 3400 - 3825 CFM


MCA¹











CPC102XXX7BXXX 17 20
EHK7-16 22 25 15 3400 - 3825 CFM 3400 - 3825 CFM
EHK7-30 41 45 30 3400 - 3825 CFM 3400 - 3825 CFM
EHK7-45 57 60 43 3400 - 3825 CFM 3400 - 3825 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon device
^ - EHK Heater Kits above require a three-phase power supply