Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC90-150 www.goodmanmfg.com 3
prodUCt speCifiCations — 7½ tons
 
CPC090
XXX3BXXX
CPC090
XXX4BXXX
CPC090
XXX3BXXX
CPC090
XXX4BXXX
CPC090
XXX7BXXX

Total BTU/h 90,000 90,000 90,000 90,000 90,000
Sensible BTU/h 65,700 65,700 64,000 64,000 64,000
EER / IEER 11.5 / 11.5 11.5 / 11.5 11.5 / 11.5 11.5 / 11.5 11.5 / 11.5
Decibels 82.0 82.0 82.0 82.0 82.0
AHRI Reference #s 3000986 3000986 3620223 3620223 3620223

Motor Type Belt Drive Belt Drive Belt Drive Belt Drive Belt Drive
Indoor Nominal CFM 3,000 3,000 3,000 3,000 3,000
Indoor Motor FLA (Cooling) 7.8 3.9 5.0 2.5 2.3
Horsepower / RPM 2.0 / 1725 2.0 / 1725 1.5 / 1745 1.5 / 1745 1.5 / 1725
Piston Size (Cooling) 0.076 0.076 0.078 0.078 0.078
Filter Size (Qty) (4) 16”x24”x2” (4) 16”x24”x2” (4) 16”x20”x2” (4) 16”x20”x2” (4) 16”x20”x2”
Drain Size (NPT) ¾” ¾” ¾” ¾” ¾”
R-410A Refrigerant Charge Cir #1 & #2 215 oz. 215 oz. 175 oz. 175 oz. 175 oz.
Evaporator Coil Face Area (²) 10.2 10.2 8.9 8.9 8.9
Rows Deep / Fins per Inch 4 / 16 4 / 16 4 / 16 4 / 16 4 / 16

# of Wheels (D x W) 1 (15” x 12”) 1 (15” x 12”) 1 (15” x 12”) 1 (15” x 12”) 1 (15” x 12”)
Motor Sheave / Blower Sheave VL40 / AK74 VL40 / AK74 VL40 / AK74 VL40 / AK74 VL40 / AK74
Belt AX51 AX51 AX51 AX51 AX51

Quanty of Condenser Fan Motors 2 2 2 2 2
Horsepower - RPM ¼ - 1090 ¼ - 890 ¼ - 1075 ¼ - 890 ¼ - 1,075
Fan Diameter / # Fan Blades 22 / 4 22 / 4 22 / 4 22 / 4 22 / 4
Outdoor Nominal CFM 7,600 7,600 7,600 7,600 7,600
Face Area (²) 32.4 32.4 26.5 26.5 26.5
Rows Deep / Fins per Inch 2 / 20 2 / 20 2 / 22 2 / 22 2 / 22

Quanty / Type 2 / Scroll 2 / Scroll 2 / Scroll 2 / Scroll 2 / Scroll
Stage 1 1 1 1 1

Voltage-Phase-Frequency 208/230-3-60 460-3-60 208/230-3-60 460-3-60 575-3-60
Quanty of Compressors 2 2 2 2 2
Compressor RLA / LRA 13.1 / 83.1 6.1 / 41.0 13.1 / 83.1 6.1 / 41.0 4.4 / 33.0
Max External Stac 1.5” 1.5” 1.0” 1.0” 1.0”
Outdoor Fan HP / RLA (2) ¼ / 1.4 (2) ¼ / 0.8 (2) ¼ / 1.4 (2) ¼ / 0.8 (2) ¼ / 0.6
Total Unit Amps 36.9 17.7 34.0 16.3 12.3
Min. Circuit Ampacity¹ 40 19 37.3 17.8 13.4
Max. Overcurrent Protecon (amps)² 50 25 50 20 15
Entrance Power Supply
Locang
Dimple
Locang
Dimple
Locang
Dimple
Locang
Dimple
Locang
Dimple
Entrance Control Voltage
 1110 1110 975 975 975
 1150 1150 1000 1000 1000
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.