Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
6 www.goodmanmfg.com SS-CPC90-150
prodUCt speCifiCations — 12½ tons
CPC150XXX
3BXXX
CPC150XXX
4BXXX
CPC150XXX
7BXXX
Cooling Capacity
Total, BTU/h 146,000 146,000 146,000
Sensible BTU/h 102,200 102,200 102,200
EER / IPLV 11.0 / 11.2 11.0 / 11.2 11.0 / 11.2
Decibels 83 83 83
ARI Reference #s 3542680 3542680 3542680
Evapoartor Motor / Coil
Motor Type Belt Drive Belt Drive Belt Drive
Indoor Nominal CFM 5,000 5,000 5,000
Indoor Motor FLA (Cooling) 9.4 4.7 4.2
Horsepower - RPM 3.0 - 1,725 3.0 - 1,725 3.0 - 1,725
Piston Size (Cooling) 0.096 0.096 0.096
Filter Size (4) 20" x 25" x 2" (4) 20" x 25" x 2" (4) 20" x 25" x 2"
Drain Size (NPT) ¾" ¾" ¾"
R-410A Refrigerant Charge Cir #1 & #2
285 oz. 285 oz. 285 oz.
Evaporator Coil Face Area (
2
) 14.7 14.7 14.7
Rows Deep / Fins per Inch 4 / 15 4 / 15 4 / 15
Condenser Fan / Coil
Quanty of condenser Fan Motors 2 2 2
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter / # Fan Blades 22/3 22/3 22/3
Outdoor Nominal CFM 7,200 7,200 7,200
Face Area (
2
) 35.3 35.3 35.3
Rows Deep / Fins per Inch 2/3 rows 15 fpi 2/3 rows 15 fpi 2/3 rows 15 fpi
Belt Drive Evap Fan Data
# of Wheels (D x W) (1) 15" x 15" (1) 15" x 15" (1) 15" x 15"
Motor Sheave / Blower Sheave VL40 / AK66 VL40 / AK66 VL40 / AK66
Belt AX49 AX49 AX49
Compressor
Quanty / Type 1 / Scroll 1 / Scroll 1 / Scroll
Stage Single Single Single
Compressor RLA / LRA ea. 22.4 / 149 10.6 / 75 7.7 / 54
Electrical Data / Static
Voltage / Phase / Frequency 208-230/3/60 460/3/60 575/3/60
Outdoor Fan FLA ea. 2.4 1.2 0.9
Total Unit Amps 59 28 21.4
Min. Circuit Ampacity
1
65 31 23
Max. Overcurrent Protecon (amps)
2
80 40 30
Entrance Power Supply
Locang
Dimple
Locang
Dimple
Locang
Dimple
Entrance Control Voltage
Operating Weight (lbs) 1275 1275 1275
Ship Weight (lbs) 1300 1300 1300
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.