Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
4 www.goodmanmfg.com SS-CPC90-150
prodUCt speCifiCations — 8½ tons
CPC102
XXX3BXXX
CPC102
XXX4BXXX
CPC102
XXX7BXXX

Total, BTU/h 102,000 102,000 102,000
Sensible BTU/h 70,380 70,380 70,380
EER / IEER 11.3 / 11.2 11.3 / 11.2 11.3 / 11.2
Decibels 83 83 83
ARI Reference #s 3620220 3620220 3620220

Motor Type Belt Drive Belt Drive Belt Drive
Indoor Nominal CFM 3,400 3,400 3,400
Indoor Motor FLA (Cooling) 7.8 3.9 2.3
Horsepower - RPM 1725 1725 1725
Piston Size (Cooling) 0.08 0.08 0.08
Filter Size (Qty) (4) 16” x 20” x 2” (4) 16” x 20” x 2” (4) 16” x 20” x 2”
Drain Size (NPT) 3/4" 3/4" 3/4"
R-410A Refrigerant Charge Cir #1 & #2 180 oz. 180 oz. 180 oz.
Evaporator Coil Face Area (2) 8.9 8.9 8.9
Rows Deep / Fins per Inch 4 / 16 4 / 16 4 / 16

# of Wheels (D x W) 1 (15" x 12") 1 (15" x 12") 1 (15" x 12")
Motor Sheave / Blower Sheave VL40 / AK74 VL40 / AK74 VL40 / AK74
Belt AX51 AX51 AX51

Quanty of Condenser Fan Motors 2 2 2
Horsepower - RPM 1/4" - 1,090 1/4" - 890 1/4" - 1,075
Fan Diameter / # Fan Blades 22 / 4 22 / 4 22 / 4
Outdoor Nominal CFM 7,600 7,600 7,600
Face Area (2) 13.25 13.25 13.25
Rows Deep / Fins per Inch 2 / 22 2 / 22 2 / 22

Quanty / Type 2 / Scroll 2 / Scroll 2 / Scroll
Stage 1 1 1

Voltage / Phase / Frequency 230 / 3 / 60 460 / 3 / 60 575 / 3 / 60
Quanty of Compressors 2 2 2
Compressor RLA / LRA ea. 14.5 / 98 6.3 / 55 6.0 / 41
Standard Max Stac 1" 1 1
Outdoor Fan FLA ea. 1.4 0.8 0.6
Total Unit Amps 39.6 18.1 15.5
Min. Circuit Ampacity¹ 43.2 19.7 17
Max. Overcurrent Protecon (amps)² 50 25 20
Entrance Power Supply
Locang
Dimple
Locang
Dimple
Locang
Dimple
Entrance Control Voltage
 975 975 975
 1000 1000 1000
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.