Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC90-150 www.goodmanmfg.com 11
heat kit eleCtriCal data (Blower only, heat mode) — 7½ tons (a modles)
minimUm airflow for eleCtriC heat
 
15 3,000
30 3,000
43 3,000
kw CorreCtion faCtors

 240 230 220 210 208
 1 0.93 0.82 0.78 0.76

 460 440 430
 0.92 0.84 0.8
For other voltage, use voltage² / 480²

 560 550 540
 0.95 0.91 0.88
Multiply rated kW by correction factor to get actual kW.


MCA¹







CPC090XXX3BXXX 40 50
EHK3-16 48 / 55 50 / 60 15 3000 - 3375 CFM
EHK3-30 87 / 100 90 / 100 30 3000 - 3375 CFM
EHK3-45 121 / 139 125 / 150 43 3000 - 3375 CFM


MCA¹







CPC090XXX4BXXX 19 25
EHK4-16 27 30 15 3000 - 3375 CFM
EHK4-30 50 50 30 3000 - 3375 CFM
EHK4-45 70 70 43 3000 - 3375 CFM


MCA¹







CPC090XXX7BXXX 14 15
EHK7-16 22 25 15 ---
EHK7-30 41 45 30 ---
EHK7-45 57 60 43 ---
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon device