prodUCt speCifiCations
prodUCt speCifiCations
14 www.goodmanmfg.com SS-CPC90-150
heat kit eleCtriCal data (Blower only, heat mode) — 10 tons
kw CorreCtion faCtor
Supply Voltage 240 230 220 210 208
Correcon Factor 1 0.93 0.82 0.78 0.76
Actual Voltage 460 440 430
Correcon Factor 0.92 0.84 0.8
For other voltage use voltage² / 480²
Supply Voltage 560 550 540
Correcon Factor 0.95 0.91 0.88
Multiply rated kW by correction factor to get actual kW
minimUm airflow for eleCtriC heat
15 4,000 4,000
30 4,000 4,000
43 4,000 4,000
MCA¹
CPC120XXX3BXXX 49 60
EHK3-16 48 / 55 50 / 60 15 3500 - 4500 CFM
EHK3-30 87 / 100 90 / 100 30 3500 - 4500 CFM
EHK3-45 121 / 139 125 / 150 43 4000 - 4500 CFM
MCA¹
CPC120XXX3HXXX 50 60
EHK3-16 49 / 57 50 / 60 15 3500 - 4500 CFM
EHK3-30 88 / 102 90 / 110 30 3500 - 4500 CFM
EHK3-45 122 / 141 125 / 150 43 4000 - 4500 CFM
MCA¹
CPC120XXX4BXXX 24 30
EHK4-16 27 30 15 3500 - 4500 CFM
EHK4-30 50 50 30 3500 - 4500 CFM
EHK4-45 70 70 43 4000 - 4500 CFM
MCA¹
CPC0120XXX7BXXX 17 20
EHK7-16 22 25 15 3500 - 4500 CFM
EHK7-30 41 45 30 3500 - 4500 CFM
EHK7-45 57 60 43 4000 - 4500 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protecon device