Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
20 www.goodmanmfg.com SS-CPC90-150
expanded Cooling data — 8½ tons

65 75  95 105 115

  59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
70
3600
MBh 100.0 103.6 113.5 - 97.6 101.2 110.9 - 95.3 98.8 108.2 - 93.0 96.4 105.6 - 88.3 91.6 100.3 - 81.8 84.8 92.9 -
S/T 0.69 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.76 0.64 0.44 - 0.79 0.66 0.46 - 0.80 0.67 0.46 -
∆T 18 15 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 15 12 - 17 14 11 -
kW 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 -
HI PR 245 263 278 - 274 295 312 - 312 336 355 - 355 382 404 - 400 430 454 - 442 475 502 -
LO PR 104 110 120 - 109 116 127 - 114 121 132 - 119 127 139 - 125 133 145 - 130 138 150 -
3200
MBh 97.0 100.6 110.2 - 94.8 98.2 107.6 - 92.5 95.9 105.1 - 90.3 93.6 102.5 - 85.8 88.9 97.4 - 79.4 82.3 90.2 -
S/T 0.66 0.55 0.38 - 0.69 0.57 0.40 - 0.70 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.44 - 0.76 0.63 0.44 -
∆T 18 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 17 15 11 -
kW 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 -
HI PR 242 261 275 - 272 292 309 - 309 332 351 - 352 379 400 - 396 426 450 - 437 471 497 -
LO PR 103 109 119 - 108 115 126 - 113 120 131 - 118 126 137 - 124 132 144 - 128 136 149 -
2800
MBh 89.6 92.8 101.7 - 87.5 90.7 99.3 - 85.4 88.5 97.0 - 83.3 86.4 94.6 - 79.2 82.0 89.9 - 73.3 76.0 83.3 -
S/T 0.64 0.53 0.37 - 0.66 0.55 0.38 - 0.68 0.57 0.39 - 0.70 0.58 0.41 - 0.73 0.61 0.42 - 0.73 0.61 0.42 -
∆T 19 16 12 - 19 16 12 - 19 16 12 - 19 17 13 - 19 16 12 - 18 15 12 -
kW 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 - 8.90 8.90 8.90 -
HI PR 235 253 267 - 264 284 299 - 300 323 341 - 341 367 388 - 384 413 436 - 424 457 482 -
LO PR 99 106
116 - 105 112 122 - 109 116 127 - 115 122 133 - 120 128 140 - 124 132 144 -
75
3600
MBh 101.6 104.7 113.3 121.6 99.3 102.2 110.6 118.8 96.9 99.8 108.0 115.9 94.6 97.4 105.4 113.1 89.8 92.5 100.1 107.4 83.2 85.7 92.7 99.5
S/T 0.79 0.71 0.53 0.34 0.82 0.73 0.55 0.36 0.84 0.75 0.57 0.37 0.87 0.77 0.59 0.38 0.90 0.80 0.61 0.39 0.91 0.81 0.61 0.39
∆T 20 19 15 11 21 19 16 11 21 19 16 11 21 19 16 11 21 19 16 11 19 18 15 10
kW 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90
HI PR 247 266 281 293 277 298 315 329 315 339 358 374 359 386 408 426 404 435 459 479 446 480 507 529
LO PR 105 111 122 129 111 118 128 137 115 122 133 142 121 128 140 149 126 135 147 156 131 139 152 162
3200
MBh 98.7 101.6 110.0 118.0 96.4 99.2 107.4 115.3 94.1 96.9 104.9 112.5 91.8 94.5 102.3 109.8 87.2 89.8 97.2 104.3 80.8 83.2 90.0 96.6
S/T 0.75 0.67 0.51 0.33 0.78 0.70 0.53 0.34 0.80 0.72 0.54 0.35 0.83 0.74 0.56 0.36 0.86 0.77 0.58 0.37 0.86 0.77 0.58 0.38
∆T 21 20 16 11 22 20 16 11 22 20 16 11 22 20 16 11 21 20 16 11 20 18 15 10
kW 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90  8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90
HI PR 245 263 278 290 274 295 312 325 312 336 355 370 355  404 421 400 430 454 474 442 476 502 524
LO PR 104 110 120 128 109 116 127 135 114 121 132 141 120 127 139 148 125 133 145 155 130 138 150 160
2800
MBh 91.1 93.8 101.5 108.9 89.0 91.6 99.1 106.4 86.8 89.4 96.8 103.9 84.7 87.2 94.4 101.3 80.5 82.9 89.7 96.3 74.6 76.8 83.1 89.2
S/T 0.73 0.65 0.49 0.32 0.75 0.67 0.51 0.33 0.77 0.69 0.52 0.34 0.80 0.71 0.54 0.35 0.83 0.74 0.56 0.36 0.83 0.74 0.56 0.36
∆T 22 20 16 11 22 20 17 11 22 20 17 11 22 20 17 12 22 20 16 11 20 19 15 11
kW 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90 8.90
HI PR 237 255 270 281 266 286 303 316 303 326 344 359 345 371 392 409 388 417 441 460 429 461 487 508
LO PR 101 107
117 124 106 113 123 131 110 117 128 137 116 123 135 143 121 129 141 150 126 134 146 155
IDB = Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions kW = Total system power
High and low pressures are measured at the liquid and sucon service valves. Amps = outdoor unit amps (comp.+fan)