Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC90-150 www.goodmanmfg.com 15
heat kit eleCtriCal data (Blower only, heat mode) — 12½ tons
kw CorreCtion faCtors

 240 230 220 210 208
 1 0.93 0.82 0.78 0.76

 460 440 430
 0.92 0.84 0.8
For other voltage, use voltage² / 480²

 560 550 540
 0.95 0.91 0.88
Multiply rated kW by correction factor to get actual kW.


MCA
1


MOP
2






CPC150***3B*** 65 80
EHK3-16 65 80 15 4000 - 5600
EHK3-30 102 110 30 4300 - 5600
EHK3-45 141 150 43 4500 - 5600


MCA
1


MOP
2






CPC150***4B*** 31 40
EHK4-16 31 40 15 4000 - 5600
EHK4-30 51 60 30 4300 - 5600
EHK4-45 71 80 43 4500 - 5600


MCA
1


MOP
2






CPC150***7B*** 23 30
EHK7-16 24 30 15 4000 - 5600
EHK7-30 43 45 30 4300 - 5600
EHK7-45 59 60 43 4500 - 5600
¹ Minimum Circuit Ampacity (standard drive)
² Maximum Overcurrent Protecon device (standard drive)