Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
8 www.goodmanmfg.com SS-CPC90-150
airflow data — 8½ tons

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.1 3467 701 1.04 3143 650 0.81
0.3 3391 746 1.12 3029 701 0.85 2607 653 0.63
0.5 3297 795 1.20 2899 751 0.91 2456 707 0.68
0.7 3250 845 1.30 2800 795 0.98
0.9 3153 887 1.38 2721 845 1.08
1.1 2688 894 1.20

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.9 3251 906 1.48
1.1 3278 962 1.68 2793 912 1.27
1.3 3321 1012 1.87 2862 968 1.47
1.5 3572 1060 2.22 2891 1020 1.64
1.7 3209 1072 2.01
1.9 3231 1116 2.19 2740 1077 1.75
2.1 3256 1156 2.31 2939 1126 2.01

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.1 3475 698 1.05 3159 657 0.83
0.3 3665 794 1.41 3318 744 1.08 3027 700 0.85 2646 660 0.65
0.5 3630 838 1.49 3255 800 1.2 2903 750 0.91 2458 706 0.65
0.7 3537 882 1.57 3177 844 1.26 2818 802 0.99
0.9 3086 888 1.36 2700 849 1.07
1.1 2563 893 1.14

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.9 3297 899 1.51
1.1 3248 953 1.62 2856 905 1.28
1.3 3336 1005 1.84 2810 959 1.41
1.5 3364 1054 2.04 2799 1016 1.59
1.7 3238 1100 2.15 2886 1066 1.81
1.9 3188 1146 2.23 2809 1111 1.97
Notes :
Assume dry coil with lter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.