Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC90-150 www.goodmanmfg.com 7
airflow data — 7½ tons

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.1 3617 704 1.07 3293 653 0.84
0.3 3541 749 1.15 3179 704 0.88 2757 656 0.66
0.5 3447 798 1.23 3049 754 0.94 2606 710 0.71
0.7 3400 848 1.33 2950 798 1.01 2474 754 0.75
0.9 3303 890 1.41 2871 848 1.11 2408 804 0.82
1.1 2838 897 1.23

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.9
DO NOT
OPERATE
3401 909 1.51
1.1 3428 965 1.71 2943 915 1.3
1.3 3471 1015 1.9 3012 971 1.5 2423 920 1.12
1.5 3722 1063 2.25 3041 1023 1.67 2503 976 1.31
1.7 3359 1075 2.04 2540 1031 1.5
1.9 3381 1119 2.22 2890 1080 1.78
2.1 3089 1129 2.04

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.1 3625 701 1.08 3309 660 0.86
0.3 3815 797 1.44 3468 747 1.11 3177 703 0.88 2796 663 0.68
0.5 3780 841 1.52 3405 803 1.23 3053 753 0.94 2608 709 0.68 2225 665 0.53
0.7 3687 885 1.6 3327 847 1.29 2968 805 1.02 2423 758 0.73
0.9 3236 891 1.39 2850 852 1.1 2352 807 0.8
1.1 2713 896 1.17

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.9
DO NOT
OPERATE
3447 902 1.54
1.1 3398 956 1.65 3006 908 1.31
1.3 3486 1008 1.87 2960 962 1.44
1.5 3514 1057 2.07 2949 1019 1.62
1.7 3388 1103 2.18 3036 1069 1.84
1.9 2959 1114 2.0
2.1 2527 1124 1.86
Notes :
Assume dry coil with lter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.