First Alert FA168CPSSIA Home Security System User Manual


 
– 5 –
31
Single Alarm Sounding Per Zone
0 = unlimited sounding
1 = one alarm sounding per zone
SIA-Compliant Controls: If “0”
selected, “alarm sounding per zone”
will be the same as the “number of
reports in armed period” set in field
*93 (1 if one report, 2 if 2 reports,
unlimited for zones in zone list 7).
[0]
If enabled, limits alarm sounding on the bell output to once per zone
per armed period.
32
Fire Alarm Sounder Timeout
0 = sound stops at timeout selected in
field 33
1 = no timeout; sounds until manually
turned off
[0]
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances. Temporal pulse soundin
g
for a
fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3
pulses.
UL: must be 1 for fire installations
33
Alarm Sounder (Bell) Timeout
0 = none 3 =12 min
1 = 4 min 4 = 16 min
2 = 8 min
[1]
This field determines whether the external sounder will shut off after
time allotted, or continue until manually turned off.
UL: For residential fire alarm installation, must be set for a minimum of 4 min
(option 1); for UL Commercial Burglary installations, must be minimum 16 min
(option 4)
34
Exit Delay
00 - 96 = 0 - 96 secs
97 = 120 secs
SIA-Compliant Controls:
45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result
in a 45-second delay.
| | [60,60]
Part. 1 Part. 2
The system waits the time entered before arming entry/exit zones. If
the entry/exit door is left open after this time expires, an alarm will
occur. Common zones use same delay as partition 1.
SIA Guidelines: minimum exit delay is 45 seconds
Common zones use part. 1 delay.
UL installations: For UL Commercial Burglar Alarm and UL Residential Burglar
Alarm installations with line security, total exit time must not exceed 60
seconds.
35
Entry Delay #1
00 - 96 = 0 - 96 seconds
97 = 120 secs
98 = 180 secs
99 = 240 secs
SIA-Compliant Controls:
30-96 = 30 - 96 secs; 97 = 120 secs;
98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result
in a 30-second delay.
| | [30,30]
Part. 1 Part. 2
Upon entering, the system must be disarmed before the time entered
expires, otherwise it sounds an alarm.
Common zones use same delay as part 1.
SIA Guidelines: minimum entry delay is 30 seconds
For UL Residential Burglary Alarm installations, must be set for a maximum of
30 seconds; entry delay plus dial delay should not exceed 1 min. For UL
Commercial Burglar Alarm, total entry delay may not exceed 45 seconds.
Upon entering, the system must be disarmed before the time entered expires,
otherwise it sounds an alarm.
36
Entry Delay #2
See *35 Entry Delay 1 for entries.
| | [30,30]
Part. 1 Part. 2
37
Audible Exit Warning
0 = no; 1 = yes
SIA-Compliant Controls: Feature
always enabled; field does not exist.
[1,1]
Part. 1 Part. 2
Warning sound consists of slow continuous beeps until the last 10
seconds, and then it changes to fast beeps. Sound ends when exit time
expires.
SIA Guidelines: must be enabled
38
Confirmation Of Arming Ding
0 = no
1 = yes (wired keypads and RF)
2 = yes, RF only (except 5827,
5827BD)
[0,0]
Part. 1 Part. 2
Confirmation of arming is 1/2-sec external sounder “ding.”
If 1 selected, ding occurs when closing report is sent if open/close
reporting is enabled, or at the end of Exit Delay. If 2 selected, ding
occurs upon reception of the wireless arming command.
UL: must be 1 for UL Commercial Burglar Alarm inst.