– 5 –
∗
∗∗
∗31
Single Alarm Sounding Per Zone
0 = unlimited sounding
1 = one alarm sounding per zone
SIA-Compliant Controls: If “0”
selected, “alarm sounding per zone”
will be the same as the “number of
reports in armed period” set in field
*93 (1 if one report, 2 if 2 reports,
unlimited for zones in zone list 7).
[0]
If enabled, limits alarm sounding on the bell output to once per zone
per armed period.
∗
∗∗
∗32
Fire Alarm Sounder Timeout
0 = sound stops at timeout selected in
field ∗33
1 = no timeout; sounds until manually
turned off
[0]
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances. Temporal pulse soundin
g
for a
fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3
pulses.
UL: must be 1 for fire installations
∗
∗∗
∗33
Alarm Sounder (Bell) Timeout
0 = none 3 =12 min
1 = 4 min 4 = 16 min
2 = 8 min
[1]
This field determines whether the external sounder will shut off after
time allotted, or continue until manually turned off.
UL: For residential fire alarm installation, must be set for a minimum of 4 min
(option 1); for UL Commercial Burglary installations, must be minimum 16 min
(option 4)
∗
∗∗
∗34
Exit Delay
00 - 96 = 0 - 96 secs
97 = 120 secs
SIA-Compliant Controls:
45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result
in a 45-second delay.
| | [60,60]
Part. 1 Part. 2
The system waits the time entered before arming entry/exit zones. If
the entry/exit door is left open after this time expires, an alarm will
occur. Common zones use same delay as partition 1.
SIA Guidelines: minimum exit delay is 45 seconds
Common zones use part. 1 delay.
UL installations: For UL Commercial Burglar Alarm and UL Residential Burglar
Alarm installations with line security, total exit time must not exceed 60
seconds.
∗
∗∗
∗35
Entry Delay #1
00 - 96 = 0 - 96 seconds
97 = 120 secs
98 = 180 secs
99 = 240 secs
SIA-Compliant Controls:
30-96 = 30 - 96 secs; 97 = 120 secs;
98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result
in a 30-second delay.
| | [30,30]
Part. 1 Part. 2
Upon entering, the system must be disarmed before the time entered
expires, otherwise it sounds an alarm.
Common zones use same delay as part 1.
SIA Guidelines: minimum entry delay is 30 seconds
For UL Residential Burglary Alarm installations, must be set for a maximum of
30 seconds; entry delay plus dial delay should not exceed 1 min. For UL
Commercial Burglar Alarm, total entry delay may not exceed 45 seconds.
Upon entering, the system must be disarmed before the time entered expires,
otherwise it sounds an alarm.
∗
∗∗
∗36
Entry Delay #2
See *35 Entry Delay 1 for entries.
| | [30,30]
Part. 1 Part. 2
∗
∗∗
∗37
Audible Exit Warning
0 = no; 1 = yes
SIA-Compliant Controls: Feature
always enabled; field does not exist.
[1,1]
Part. 1 Part. 2
Warning sound consists of slow continuous beeps until the last 10
seconds, and then it changes to fast beeps. Sound ends when exit time
expires.
SIA Guidelines: must be enabled
∗
∗∗
∗38
Confirmation Of Arming Ding
0 = no
1 = yes (wired keypads and RF)
2 = yes, RF only (except 5827,
5827BD)
[0,0]
Part. 1 Part. 2
Confirmation of arming is 1/2-sec external sounder “ding.”
If 1 selected, ding occurs when closing report is sent if open/close
reporting is enabled, or at the end of Exit Delay. If 2 selected, ding
occurs upon reception of the wireless arming command.
UL: must be 1 for UL Commercial Burglar Alarm inst.