Envision Peripherals R-410A Heat Pump User Manual


 
16
ENVISION RESIDENTIAL INSTALLATION MANUAL
Setting Fan Speed - PSC
CAUTION: Disconnect all power before
performing this operation.
Fan Performance Data - PSC
PSC FAN MOTOR BODY
HIGH
LOWMEDIUM
F
A
N
S
P
E
E
D
W
I
R
E
Fan Blower Motor Airflow (cfm) at External Static Pressure (in. wg)
Model Spd Size HP 0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
H 1110 1095 1080 1065 1045 1020 995 970 945 915 880 810 ----
M 9 x 71/5850845835825815805795775755735715-----
L 750745740735725715700685670650630-----
H 1290 1270 1245 1220 1190 1160 1125 1090 1055 1020 985 880 760 - - -
M 9 x 7 1/3 1100 1090 1075 1060 1045 1020 995 970 940 910 875 785 625 - - -
L 910 905 900 895 885 875 865 850 835 810 780 710 560 - - -
H 1665 1640 1610 1580 1550 1515 1480 1450 1415 1315 1215 1090 980 - - -
M 9 x 7 1/2 1465 1445 1425 1400 1375 1350 1325 1260 1190 1140 1090 990 890 - - -
L 1130 1115 1100 1090 1075 1035 995 965 930 895 860 795 730 - - -
H 2010 1975 1940 1905 1870 1825 1780 1735 1690 1640 1590 1470 1210 - - -
M 10 x 10 1/2 1670 1650 1630 1610 1590 1560 1530 1495 1460 1425 1390 1190 1080 - - -
L 1220 1215 1210 1295 1200 1180 1160 1130 1100 1060 1020 930 ----
H 2010 1975 1940 1905 1870 1825 1780 1735 1690 1640 1590 1470 1210 - -
M 10 x 10 1/2 1670 1650 1630 1610 1590 1560 1530 1495 1460 1425 1390 1190 1080 - - -
L 1220 1215 1210 1295 1200 1180 1160 1130 1100 1060 1020 930 ----
H 2430 2400 2365 2330 2290 2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330
M 11 x 10 1 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260
L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1175
H 2430 2400 2365 2330 2290 2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330
M 11 x 10 1 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260
L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1175
Fan Blower Motor Airflow (cfm) at External Static Pressure (in. wg)
Model Spd Size HP 0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
H 1290 1270 1245 1220 1190 1160 1125 1090 1055 1020 985 880 760 - - -
M 9 x 7 1/3 1100 1090 1075 1060 1045 1020 995 970 940 910 875 785 625 - - -
L 910 905 900 895 885 875 865 850 835 810 780 710 560 - - -
H 1365 1340 1325 1305 1280 1250 1215 1180 1140 1100 1055 960 850 - - -
M 9 x 7 1/2 1040 1040 1035 1030 1020 1005 990 970 945 915 885 810 735 - - -
L 880 880 880 880 875 870 860 840 820 800 775 730 480 - - -
H 1930 1905 1875 1840 1805 1765 1725 1680 1635 1530 1425 1270 1150 1025 - -
M 9 x 7 1/2 1635 1620 1600 1580 1555 1530 1505 1465 1425 1335 1240 1135 1035 775 - -
L 1230 1230 1225 1215 1200 1165 1130 1095 1060 1035 1005 935 795 675 - -
H 2115 2075 2035 1980 1920 1900 1880 1840 1795 1730 1660 1390 1225 1070
1070
--
M 10 x 10 3/4 2005 1980 1950 1910 1865 1815 1765 1725 1685 1585 1485 1315 1140 1025 - -
L 1860 1835 1805 1780 1750 1715 1675 1635 1590 1540 1490 1260 1115 980 - -
H 2115 2075 2035 1980 1920 1900 1880 1840 1795 1730 1660 1390 1225 - -
M 10 x 10 3/4 2005 1980 1950 1910 1865 1815 1765 1725 1685 1585 1485 1315 1140 1025 - -
L 1860 1835 1805 1780 1750 1715 1675 1635 1590 1540 1490 1260 1115 980 - -
Factory settings are in Bold
High-Static option not available for 060 and 070
Air flow values are with dry coil and standard filter
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg.
and 500 fpm by 0.16 in. wg.
022
030
036
042
048
060
070
022
030
036
042
048
Standard PSC Motor
Optional High Static PSC Motor