9.0 SYSTEM OPERATION, TESTING AND MAINTENANCE
This section describes system testing, maintenance and replacement procedures. Use copies of the
Maintenance Inspection Checklist to record preventive maintenance inspections.
9.1 System Testing
9.1.1 Environmental Control Functions
The performance of all control circuits can be tested by changing the set points, which activates each
of the main functions.
9.1.2 Cooling
To test the cooling function, set the set point to a temperature of 10°F (5°C) below room temperature.
A call for cooling should register and prompt the equipment to begin cooling cycle. (Disregard any
temperature alarms). Upon completion of testing, return set point to the desired temperature.
9.1.3 Heating
Reheat may be tested by setting the set point 10°F (5°C) above room temperature. A call for heating
should register and prompt the equipment to begin heating cycle. (Disregard any temperature
alarms). Upon completion of testing, return set point to the desired temperature.
9.1.4 Humidification
To check humidification, set the humidity set point at R.H. 10% above the room humidity reading.
After a short delay, the canister will fill with water and steam will be produced. Upon completion of
testing, return the humidity set point to the desired humidity.
9.1.5 Dehumidification
The dehumidification performance can be tested by setting the humidity set point at R.H. 10% below
room relative humidity. The compressor should turn on. Upon completion of testing, return humidity
set point to the desired humidity.
9.1.6 Remote Shutdown
A connection point is provided for remote shutdown devices supplied by the customer. This terminal
strip is located on the printed circuit board. (Terminals TB1-4 and TB1-5 are fitted with a jumper
when no remote shutdown device is installed).
9.2 Maintenance and Component Operation
9.2.1 Electric Panel
The electric panel should be inspected on a semi-annual basis for any loose electrical connections.
9.2.2 Filters
Filters are usually the most neglected item in an environmental control system. In order to maintain
efficient operation, they should be checked monthly and changed as required. ALWAYS TURN
POWER OFF BEFORE REPLACING FILTERS.
Filters are replaced by opening the hinged door on the return air filter box.
!
WARNING
Risk of electric shock. Can cause injury or death.
Open all local and remote electric power disconnect switches before working within the
electrical enclosures.
The Liebert microprocessor control does not isolate power from the unit in the Unit Off mode.
Some internal components require and receive power even during the Unit Off mode. The line
side of the disconnect switch on the front of the unit contains live high voltage. The only way
to ensure that there is NO voltage inside the unit is to install and open a remote disconnect
switch and check the internal power supply wires with a voltmeter.