Emerson MINI-MATE2 Fan User Manual


 
Site Preparation and Installation
Liebert
®
Mini-Mate2
32
Figure 20 Dimensions—Air-cooled systems, high ambient and Quiet-Line condensing module
5.6.2 Piping Connections
Details for refrigerant loop piping are in 5.4.3 - Piping Connections and Coolant Requirements.
5.6.3 Electrical Connections
Refer 5.4.4 - Electrical Connections for general wiring requirements and cautions. Refer to
electrical schematic when making connections.
Power Connections
The outdoor condensing unit requires its own power source and earth ground, with a disconnect
switch (field supplied) to isolate the unit for maintenance.
Control Connections
Field-supplied control wires must be connected between the evaporator and the condensing unit. (See
Figure 14 and the electrical schematic on the units for more details.) Four wires are required
between the evaporator and condensing unit.
Table 15 Net weight, high ambient and Quiet-Line condensing modules, air-cooled systems
Model # Module
Net Weight
lb. (kg)
60Hz 50Hz
PFH067A- H
PFHZ67A- L
PFH066A- H
PFHZ66A-L
488 (222)
DPN000131
Rev. 0
36-1/4" (918)
38-1/2"
(978)
53"
(1346mm)
Right Air
Intake
Top Air
Discharge
Guard Height
5-1/2" (140mm)
Left Air
Intake
Shaded area indicates
a minimum clearance of
18" (457mm) for proper
air flow
Shaded area indicates
a minimum clearance of
18" (457mm) for proper
air flow
Shaded area indicates
a minimum clearance of
24" (610mm) for component
access and removal
Removable front panel
for access to high-voltage
and low-voltage connections
and to refrigeration components
2"
(51mm)