Emerson MINI-MATE2 Fan User Manual


 
Microprocessor Control
Liebert
®
Mini-Mate2
44
6.12 Alarm Enable
Each alarm can be disabled or enabled. Use the Up and Down arrows to select a particular alarm,
press Enter to select either Enable or Disable. Press Enter again to store the change. When the alarm
is disabled it will NOT report to either the wall box beeper or to the common alarm relay.
6.13 Alarm Time Delay
Each individual alarm can be programmed with a time delay, causing the unit to delay a specified
amount of time (0-255 seconds) before recognizing the alarm. See Table 19 for the default times. The
alarm condition must be present for the full amount of the time before the alarm will sound. If the
alarm condition is diverted prematurely, the alarm will not be recognized and the time delay will
automatically reset.
6.14 Common Alarm Enable
Each individual alarm can be selected to activate or deactivate the common alarm relay. If the
energize common alarm function is set to Yes, the relay is energized immediately as the alarm is
annunciated and de-energized when the alarm condition has been recognized. If the alarm is
completely Disabled, the alarm has no effect on the common alarm relay. Use the Up and Down
arrows to scroll to a particular alarm, press the Enter button to select it, then press the Enter button
again to select Yes or No.
NOTE
The high-water alarm will automatically shut the unit Off, even if the alarm is disabled.
Similarly, optional factory-installed smoke sensor is wired to shut off the evaporator unit,
regardless of the enable/disable status.
NOTE
For software alarms such as “loss of power” and “short cycle,” the time delay should be left at
the factory default of 0.
Table 19 Alarm default time delays
Alarm
Default Time Delay
(seconds)
Custom Alarm #1 0
Custom Alarm #2 6
High Temperature 30
Low Temperature 30
High Humidity 30
Low Humidity 30
Short Cycle 0
Loss of Power 0