5.6 Outdoor Air-Cooled Condensing Unit Installation
5.6.1 Location Considerations
To ensure a satisfactory air supply, locate air-cooled propeller fan condensing units in an environment
providing clean air, away from loose dirt and foreign matter that may clog the coil. Condensing units
must not be located in the vicinity of steam, hot air or fume exhausts or closer than 18 inches from a
wall, obstruction or adjacent unit. Avoid areas where heavy snow will accumulate at air inlet and
discharge locations.
The condensing unit should be located for maximum security and maintenance accessibility. Avoid
ground-level sites with public access.
Install a solid base, capable of supporting the weight of the condensing unit. The base should be at least
2 inches higher than the surrounding grade and 2 inches larger than the dimensions of the condensing
unit base. For snowy areas, a base of sufficient height to clear snow accumulation must be installed.
Figure 19 Dimensions—Air-cooled systems, standard ambient outdoor condensing module
NOTE
Follow all national and local building, electrical and plumbing codes.
Table 14 Weights for standard ambient outdoor condensing modules, air-cooled systems
Model #
Weight, lb (kg)
60Hz 50Hz
PFH067A-L PFH066A-L 351 (159)
53"
(1343mm)
36-1/4"
(918mm)
C
DPN000130
Rev. 1
Removable (Right) Panel
for Access to Refrigeration Component
Right Air
Discharge
Left Air
Intake
Fan Rotation
Counteclockwise
(left side)
Shaded area indicates
a minimum clearance of
18" (457mm) for proper
air flow
Shaded area indicates
a minimum clearance of
18" (457mm) for proper
air flow
Shaded area indicates
a minimum clearance of
24" (610mm) for component
access and removal
Removable front panel
for access to high-voltage
and low-voltage connections
and to refrigeration components
18"
(457mm)