Crown Boiler 32 Boiler User Manual


 
9
III Before Installing
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict
accordance with this manual and the requirements of the authority having jurisdiction.
In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest
edition of the National Fuel Gas Code, ANSI Z223.1.
Where required by the authority having jurisdiction, this installation must conform to the latest edition of the
Standard for Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1)
2) Make sure that a properly sized chimney is available and is in good condition. Consult the authority having
jurisdiction, Part VII of this manual, and the National Fuel Gas Code for additional information on venting
requirements.
3) Make sure that the boiler is correctly sized.
4) This boiler is designed and listed for use with natural gas only.
5) Boilers installed at altitudes above 2000 ft. require different main burner orifice than those at sea level. Make sure that
the boiler is configured for use at the correct altitude.
6) If this boiler was received as a knockdown boiler, follow the instructions in Section V to assemble the boiler.
IV Locating the Boiler
1) Minimum required boiler room volumes are shown in Table 2. To find the volume of the boiler room calculate:
Boiler Room Volume (ft
3
) = Length (ft) x Width (ft) x Height (ft)
If the height is greater than 8 ft for the room height, use 8 ft for the height in the above equation.
2) Observe the minimum clearances as shown in Table 3. These clearances apply to all combustible construction, as well as
noncombustible walls, ceilings and doors. Also see Figure 3.
3) This boiler must be installed on a non-combustible floor. A concrete pad is not sufficient to protect combustible
flooring.
4) The boiler must be installed on a hard level surface.
5) Do not install this boiler in a location where gasoline or other flammable vapors or liquids will be stored or used. Do
not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop.
7
WARNING
All Series 32 boilers must be installed in rooms that are large in comparison with the size of
the equipment and must be installed with the clearances listed in Table 2. Such a room will
have a volume equal to at least 16 times the total volume of the boiler.
WARNING
This Product Must be Installed By A Licensed Plumber Or Gas Fitter when Installed Within
The Commonwealth Of Massachusetts.
If This Boiler is Equipped With a Tankless Heater, Tankless Heater Piping Must be Installed
by a Licensed Plumber When Boiler is Installed Within the Commonwealth of Massachusetts.