Crown Boiler 32 Boiler User Manual


 
59
12) Place the boiler back in operation using the procedure outlined in “Start-up”. Check the pilot line and any other
gas piping disturbed during the inspection process for leaks.
Heat Exchanger Cleaning Procedure
1) Turn off electrical power and gas supply to the boiler
2) Disconnect the vent connectors from the boiler.
3) Remove the front, top and rear jacket panels.
4) Remove the burners.
5) Remove the nuts and washers holding the flue collector onto the heat exchanger.
6) Carefully remove the flue collector gasket strips and set them aside.
7) Remove the flue collector from the heat exchanger.
8) Clean the flue passageways using a stiff bristle brush. Be certain that all foreign material is removed from the
gaps between the pins.
9) Clean the bottom surfaces of the heat exchanger.
10) Put a light in the combustion chamber and look through the flue passages from the top to verify that they have
been thoroughly cleaned.
11) Replace the flue collector gasket strips.
12) Replace the nuts and washers that hold down the flue collector.
13) Reattach all the jacket components.
14) Reinstall burners, being careful to put the pilot main burner in its’ original location.
15) Reconnect the vent system.
WARNING
SOOT DEPOSITS IN THE FLUE PASSAGES ARE A SIGN THAT THE BOILER MAY BE OPERATING AT HIGH
CARBON MONOXIDE (CO) LEVELS. AFTER CLEANING THE BOILER OF SOOT DEPOSITS, CHECK THE CO
LEVEL IN THE FLUE GAS TO INSURE THAT THE BOILER IS OPERATING PROPERLY.
If it is necessary to check CO, use a combustion analyzer, or other instrument which is designed to measure CO in flue gas.
A CO “sniffer” designed for testing CO levels in ambient air cannot be used to check boiler combustion. Take a flue gas
sample by inserting a sample probe through the draft diverter opening and into the flue collector so that the sample is taken
in the area directly over the heat exchanger. Do not take a sample until the boiler has been firing for at least five minutes.
A normal CO reading for a Series 32 boiler is less than 50ppm (0.005%). A reading of more than 100ppm (0.01%) is
indicative of a combustion problem.
Some causes of excessive CO include:
Incorrectly sized main burner orifice for the altitude at which boiler is installed
Crooked or out-of-round orifice holes (never attempt to drill orifice for this boiler in the field)
Partially plugged flue passages
Improper manifold pressure
Foreign material in burner venturis or burner ports
Inadequate supply of combustion air
57