Carrier EK Gas Heater User Manual


 
The alarm codes for the IGC control board are shown in
Table 22.
Table 22 IGC Control Board LED Alarms
INDICATION ERROR MODE
ON Normal Operation
OFF Hardware Failure
1 FLASH Fan ON/OFF Delay Modified
2 FLASHES Limit Switch Fault
3 FLASHES Flame Sense Fault
4 FLASHES 4 Consecutive Limit Switch Faults
5 FLASHES Ignition Lockout Fault
6 FLASHES Induced Draft Motor Fault
7 FLASHES Rollout Switch Fault
8 FLASHES Internal Control Fault
Diagnostic LEDs There are 3 LEDs (red, yellow,
and green) on the lower right hand side of the control board.
The red light is used to check unit operation and alarms. A
constant pulse is normal unit operation. A series of quick
blinks indicates an alarm. Refer to Table 23 below for a de-
scription of alarms. The yellow LED blinks during transmis-
sion with the CCN (Carrier Comfort Network). The green
LED blinks during transmission with the expansion board.
Table 23 Control Board LED Alarms
LED Blinks Error Code Description Troubleshooting Comments
1 Normal Operation
The expansion board and control board flash the red LED in one-second
intervals when the board is operating properly.
2 HF-13 Compressor 1 Safety
The high orlow pressure safety switch for compressor no.1 has opened for
3 seconds. The error will be cleared and compressor no. 1 will be allowed
to turn on in 15 minutes. If the safeties have been tripped 3 times in 90 min-
utes, compressor no. 1 will be locked out until the control board has been
manually reset.
3 HF-14 Compressor 2 Safety
The high orlow pressure safety switch for compressor no.2 has opened for
3 seconds. The error will be cleared and compressor no. 2 will be allowed
to turn on in 15 minutes. If the safeties have been tripped 3 times in 90 min-
utes, compressor no. 2 will be locked out until the control board has been
manually reset.
4 HF-15 Thermostat Failure
The thermostat iscalling for both heating and cooling at the same time. The
unit will operate on a first call basis and will automatically reset.
5 HF-05 SAT Thermistor Failure
The supply-air temperature (SAT) sensor has failed. First check for wiring
errors, then replace sensor.
6 HF-06 OAT Thermistor Failure
The outside air temperature (OAT) sensor has failed. First check for wiring
errors, then replace sensor.
7 HF-03 Space Temp. Sen. Failure
The space temperature sensor has failed. First check for wiring errors, then
replace sensor.
8 HF-12 RAT Thermistor Failure
The return-air temperature (RAT) sensor has failed. Ensure that the unit is
a VAV unit. If NOT a VAV unit set DIP switch position 1 to the closed position
and reset power. Then check for wiring errors. Finally, replace sensor.
9 SE-05
Loss of Communications
with Expansion Board
Communications between the expansion board and the control board have
been interrupted. Ensure that an expansion board is installed and wired us-
ing the wire harness supplied with the expansion module. If an expansion
board is not used ensure that DIP switch position 3 is in theclosed position,
and reset power.
10 HF-16 Control Board Failure
Generated when hardware has failed on control board. Replace the control
board.
11 HF-17 Expansion Board Failure
Generated when hardware has failed on the expansion board. Replace the
expansion board.
DIP Dual In-Line Package
VAV Variable Air Volume
60