Carrier 58HDV Furnace User Manual


 
28
Rubber Coupling
&Clamps
90
°
Elbow
Combustion
Blower
Vent Fitting
&Clamps
Vent Extension
Pipe (Side Panel
Exit)
Vent Pipe
(Top PanelExit)
Vent Pipe
Rotate downward
5
°
to 10
°
NOTE: Built--in channel will be angled 5° to 10° also.
SIDE VIEW
NOTE: The 90° elbow is approved
for use inside the furnace ONLY.
Tee
A07714
Fig. 21 -- Proper Sealing Procedure for Combustion Blower
Joining Pipe and Fittings
SEE VENT AND COMBUSTION AIR PIPING, Vent a nd
Combustion Air Piping Guidelines in this manual for applicable
ASTM Standards for vent materials.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Do NOT use solvent cement that has become curdled, lumpy
or thickened and do NOT thin. Observe precautions printed
on containers. For applications below 32_F(0_C), use only
low temperature type solvent cement. Poor joints may lead to
disconnected or leaking vent pipe joints allowing carbon
monoxide to enter the living space.
!
WARNING
1. Cut pipe end square, remove ragged edges and burrs.
Chamfer end of pipe, then clean fitting, socket and pipe joint
of all dirt, grease, or moisture.
NOTE: Stir the solvent cement frequently while using. Use a
natural bristle brush or the dauber supplied with the cement. The
proper brush size is one inch.
2. After c hecking pipe and socket for proper fit, wipe socket
and pipe with cleaner-primer. Apply a liberal coat of primer
to inside surface of socket and outside of pipe. Do NOT
allow primer to dry before applying cement.
3. Apply a thin coat of cement evenly in the socket. Quickly
apply a heavy coat of cement to the pipe end and insert pipe
into fittings with a slight twisting movement until it bottoms
out.
NOTE: Cement MUST be fluid while inserting pipe. If NOT,
recoat pipe.
4. Hold the pipe in the fitting for 30 seconds to prevent the
tapered socket from pushing the pipe out of the fitting.
5. Wipe all e xcess cement from the joint with a rag. Allow 15
minutes before handling. Cure time varies according to fit,
temperature and humidity.
Connecting Vent Pipes and Termination
NOTE: Combustion air intake and vent MUST terminate in the
same atmospheric pressure zone. If installation is in a cold climate
(sustained temperatures 0°F(--17°C) and below for 24 or more
consecutive hours), increase the minimum distance between vent
pipe and air intake from 8(203.2mm) to 18(457.2mm).
CARBON MONOXIDE POISONING HAZARD
Failure to properly vent this furnace could result in personal
injury or death.
Maintain a minimum of 36 (914.4mm) between
combustion air inl et and clothes dryer vent. Terminate
the com bustion air intake as far as possible from any
air conditioner, heat pump, swimming pool,
swimming pool pumping, chlorinator or filtration unit.
!
WARNING
1. Install all couplings, nipples and elbows using proper
procedures for Joining Pipe and Fittings and maintain
spacing between vent and combustion air piping as indicated
in Fig. 22through 30.
8” (203.2mm)* MIN.
20’ (6.1m)MAX
8” (203.2mm) MIN.
*18
(457.2mm) Minimum for
cold climates [sustained 0
_
F
(-17
_
C) and below for 24 or
more consecutive hours]
25--00--05F
GRADE LEVEL
OR
SNOW LEVEL
12 ”(304.8mm)MIN.
A07715
Fig. 22 -- Sidewall Termination 12” (304.8 mm) or More Above
Snow Level or Grade Level
Horizontal Termination
1. Cut two holes. 2
1
/
2
(63.5mm) for 2 (50.mm) pipe, 3
(76.2mm) for 2
1
/
2
(63.5mm) pipe, or 3
1
/
2
(88.9mm) for 3
(76.2mm) pipe. Do NOT make the holes oversized, or it will
be necessary to add a sheet metal or plywood plate on the
outside with the correct size hole in it.
2. Check hole sizes by making sure it is smaller than the
couplings or elbows that will be installed on the outside. The
couplings or elbows MUST prevent the pipe from being
pushed back through the wall.
3. Extend vent pipe and combustion air pipe through the wall
3
/
4
(19.1mm) to 1 (25.4mm) and seal area between pipe
and wall.
4. Install the couplings, nipple and termination elbows as
shown and maintain spacing between vent and combustion
air piping as indicated in Fig. 22 and Fig. 23.
A metal shield is recommended 18 x18 (457.2mm x 457.2mm)
min. or 18 (457.2mm) min. diameter around the vent termination
at the exterior wall to protect the house exterior materials from flue
product or condensation (freezing) damage.
58HDV