Carrier 52S Air Conditioner User Manual


 
INDOOR THERMOSTAT (Heat Pump Units) (cont)
(Figure 54) To verify operation of the heat pump in-
door thermostat switch, a continuity test may be per-
formed as follows:
1. Turn off unit power as described in GENERAL
DISASSEMBLY section.
2. Remove wire leads from thermostat. Note their loca-
tions to ease re-assembly.
3. To test stage A, place one lead of the continuity
tester on the terminal marked 2, and the other lead
on either the terminal marked 1 or the terminal
marked 3.
4. Adjust the thermostat up or down to verify the con-
tacts of the switch open and close. When verifying
continuity of the closed switch, the reading on the
meter should be 0 ohms. An open switch will show OL
on the meter.
5. To test stage B contacts, place one lead of the conti-
nuity tester on contact 5 and the other lead on either
contact 4 or contact 6.
6. Adjust the thermostat up or down to verify the con-
tacts of the switch open and close as in Step 4.
7. When testing is complete, reconnect the leads.
OUTDOOR FROST THERMOSTAT (Heat Pump Units)
(Figure 55) The Outdoor Frost Thermostat (OFT) is
a thermostat that uses a single-pole switch with a
manual override selector. The thermostat switches be-
tween electric heat and compressor operation when the
temperature of the outdoor coil falls below 15 F or
rises above 35 F. Switching the override selector to elec-
tric heat disables the reverse cycle operation of the
thermostat is manually switched to electric heat opera-
tion, the compressor is disabled for heating and cool-
ing operations.
To verify the OFT is operational, a continuity test may
be performed as follows:
1. Turn off unit power as described in GENERAL
DISASSEMBLY section.
2. Remove the leads from the OFT. Note their locations
to ease re-assembly.
3. Connect the continuity tester to the switch terminals
marked 1 and 2.
4. Rotate the override switch to the electric heat setting
and verify that there is continuity between termi-
nals 1 and 2.
5. To check the other contacts, move the lead on termi-
nal 1 to terminal 3. Rotate the override switch to the
heat pump setting. There should now be continuity
between terminals 2 and 3.
6. Once the test is complete, reconnect the leads.
LEGEND (Figures 53 - 55)
COMP Compressor
FCS Fan Control Switch
IT Indoor Thermostat
OFT Outdoor Frost Thermostat
OL Overload
PLS Primary Limit Switch
SLS Secondary Limit Switch
TBH Thermostat Bulb Heater
ORN
BLK
BLU
GRY
BRN
IT
2
1
3
4
6
5
FIGURE 54 INDOOR THERMOSTAT (IT)
CONTACTS, ALL 52SQ AA AND CP MODELS
FIGURE 55 — OUTDOOR FROST THERMOSTAT (OFT)
CONTACTS, ALL 52SQ AA AND CP MODELS
52S
SERIES
28