Bryant 581C024--060 Air Conditioner User Manual


 
48
C06142
Fig. 54 --- Cooling Charging Chart,
Standard 581B 072
C06143
Fig. 55 --- Cooling Charging Chart, 581B 036 with
Optional Perfect Humidity Adaptive Dehumidification
System
C06144
Fig. 56 --- Cooling Charging Chart, 581B 048 with
Optional Perfect Humidity Adaptive Dehumidification
System
NOTE: When using the charging charts, it is important that only
the subcooling/reheat dehumidification coil liquid line solenoid
valve be energized. The subcooling/reheat dehumidification coil
liquid line solenoid valveMUST be energized to use the charging
charts and the outdoor motor speed controller jumpered to run the
fanatfullspeed.
The charts reference a liquid pressure (psig) and temperature at a
point between the condenser coil and the subcooling/reheat
dehumidification coil. A tap is provided on the unit to measure
liquid pressure entering the subcooling/reheat dehumidification
coil.
IMPORTANT: The subcooling mode charging charts (Fig.
55--58) are to be used ONLY with units having the Perfect
Humidity adaptive dehumidification system. DO NOT use
standard charge (Fig. 51--54 and 59 --62) for units with Perfect
Humidity system, and DO NOT use Fig. 55 --58 for standard
units.
581B,C