Bryant 581C024--060 Air Conditioner User Manual


 
28
Table 13—581B Outdoor Sound Power(Total Unit)
U
N
I
T
ARI
R
A
T
I
N
G
OCTAVE BANDS
UNIT
RATING
(decibels)
63 125 250 500 1000 2000 4000 8000
036, 048
76 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3
060, 072
80 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0
LEGEND
ARI --- AirConditioningand Refrigeration Institute
Table 14—581C Outdoor Sound Power(Total Unit)
U
N
I
T
ARI
RATING
A ---
W
E
I
G
H
T
E
D
OCTAVEBANDS
U
N
I
T
R
A
T
I
N
G
(decibels)
W
E
I
G
H
T
E
D
(db)
63 125 250 500 1000 2000 4000 8000
024---048 76 76 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3
060 80 80 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils. See Table 11 and Fig. 38 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the
fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
See Tables 8 and 9 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.
4. Interpolation is permissible. Do not extrapolate.
Table 15—Fan Performance 581C 024 — Vertical Discharge Units; Standard Motor (Belt Drive)**
A
I
R
F
L
O
W
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(
C
f
m
)
0.1 0.2 0.4 0.6 0.8 1.0
(
C
f
m
)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bh p
Rpm Bhp
600
500 0.08 531 0.08 607 0.14 713 0.21 788 0.29
878 0.37
700
529 0.09 567 0.09 633 0.16 739 0.24 816 0.32
902 0.41
800
547 0.10 592 0.12 660 0.19 761 0.27 845 0.37
937 0.47
900
570 0.13 620 0.14 691 0.22 793 0.32 870 0.42
957 0.53
1000
599 0.15 650 0.16 717 0.26 818 0.36 894 0.47
981 0.58
581B,C