Bryant 581C024--060 Air Conditioner User Manual


 
26
Table 7—CO
2
Sensor Standard Settings
SETTING EQUIPMENT OUTPUT
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
CO
2
CONTROL RANGE
(ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
1
Proportional Any
0-10V
4-20 mA
0-2000 1000 50
2
Interface w/Standard
BuildingControl System
Proportional Any
2-10V
7-20 mA
0-2000 1000 50
3
B
u
i
l
d
i
n
g
C
o
n
t
r
o
l
S
y
s
t
e
m
Exponential Any
0-10V
4-20 mA
0-2000 1100 50
4
Proportional 15
0-10V
4-20 mA
0-1100 1100 50
5
E
c
o
n
o
m
i
z
e
r
Proportional 20
0-10V
4-20 mA
0- 900 900 50
6
Economizer
Exponential 15
0-10V
4-20 mA
0-1100 1100 50
7
Exponential 20
0-10V
4-20 mA
0- 900 900 50
8
Health & Safety Proportional
0-10V
4-20 mA
0-9999 5000 500
9
Parking/Air Intakes/
LoadingDocks
Proportional
0-10V
4-20 mA
0-2000 700 50
LEGEND
ppm —PartsPer Million
6000
5000
4000
3000
2000
1000
0
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
DELTAP IN. WG
4&5ton
6 ton
3 ton
C06133
Fig. 41 --- Perfect Humidityt Adaptive Dehumidification System Static Pressure Drop (in. wg)
C06134
Fig. 42 --- Belt Drive Motor Mounting
C06041
Fig. 43 --- Indoor--Fan Pulley Adjustment
581B,C