VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS
A. Disconnect Switch
The optional disconnect switch is non-fused. The switch has
the capability of being locked in place for safety purposes.
B. Perfect Humidity™ Dehumidification System
Perfect Humidity system operation can be controlled by field
installation of a Bryant-approved humidistat device (Fig. 13),
or light commercial Thermidistat™ device (Fig. 14). To install
the humidistat device:
1. Route humidistat cable through hole provided in unit
corner post.
2. Feed wires through the raceway built into the corner
post to the 24-v barrier located on the left side of the
control box. See Fig. 12. The raceway provides the
UL-required clearance between high-voltage and low-
voltage wiring.
3. Use a wire nut to connect humidistat cable into low-
voltage wiring as shown in Fig. 15.
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in
unit corner post.
2. Feed the wires through the raceway built into the cor-
ner post to the 24-v barrier located on the left side of
the control box. See Fig. 12. The raceway provides the
UL-required clearance between high and low voltage
wiring.
3. A field-supplied relay must be installed between the
Thermidistat device and the Perfect Humidity circuit
(recommended relay: HN612KK324). See Fig. 16. The
relay coil is connected between the DEHUM output
and C (common) of the unit. The relay controls the
Perfect Humidity solenoid valve and must be wired
between the Perfect Humidity fuse and the low-pres-
sure switch. Refer to the installation instructions
included with the Bryant Light Commercial Thermi-
distat device for more information.
% RELATIVE HUMIDITY
Fig. 13 — Accessory Field-Installed Humidistat Device
Fig. 14 — Light Commercial Thermidistat Device
Fig. 15 — Typical Perfect Humidity Dehumidification System
Humidistat Wiring (208/230-v Unit Shown)
C—Contactor (Compressor)
CB Circuit Breaker
CR Cooling Relay
DHR Dehumidify Relay
DSV Discharge Solenoid Valve
HU Humidistat
LPS
Low Pressure Switch
LSV Liquid Line Solenoid Valve
LTLO
Low Temperature Lockout
TRAN Transformer
Terminal (Unmarked)
Splice
Factory Wiring
Accessory or Optional Wiring
LEGEND