Bryant 581A Air Conditioner User Manual


 
—21—
Table 9 — Fan Performance — 581A180360 (High Heat Units)
LEGEND
*Standard low-medium static drive range is 873 to 1021 rpm. Alternate
high-static drive range is 1025 to 1200. Other rpms require a field-
supplied drive.
NOTES:
1. Maximum continuous bhp for the standard motor is 6.13. The maxi-
mum continuous watts is 5180. Do not adjust motor rpm such that
motor maximum bhp and/or watts is exceeded at the maximum
operating cfm.
2. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Fan Performance table.
3. Interpolation is permissible. Do not extrapolate.
4. Fan performance is based on wet coils, clean filters, and
casing losses. See Table 13 for accessory/FIOP static pressure
information.
5. Extensive motor and drive testing on these units ensures that the full
bhp and watts range of the motor can be utilized with confidence.
Using your fan motors up to the watts or bhp rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
6. Use of a field-supplied motor may affect wiring size. Contact your
Bryant representative for details.
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2040.60.81.0
Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp
4500
753 1307 1.53 786 1404 1.65 861 1644 1.93 932 1893 2.22 997 2150 2.52
4800
747 1384 1.62 818 1603 1.88 890 1852 2.17 958 2108 2.47 1022 2373 2.78
5100
775 1571 1.84 850 1822 2.14 920 2079 2.44 986 2344 2.75 1048 2616 3.07
5700
849 2054 2.41 918 2323 2.73 982 2598 3.05 1044 2879 3.38 1102 3166 3.71
6000
886 2329 2.73 952 2607 3.06 1015 2891 3.39 1074 3180 3.73 1130 3474 4.08
6300
924 2628 3.08 987 2915 3.42 1047 3207 3.76 1105 3504 4.11 1160 3807 4.46
6600
962 2951 3.46 1023 3246 3.81 1081 3547 4.16 1136 3853 4.52 1190 4163 4.88
6900
1000 3298 3.87 1059 3603 4.23 1115 3912 4.59 1168 4225 4.96 1220 4543 5.33
7200
1038 3672 4.31 1095 3986 4.67 1149 4303 5.05 1201 4625 5.42 1251 4950 5.81
7500
1077 4072 4.78 1131 4394 5.15 1184 4720 5.54 1234 5050 5.92
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.21.41.61.82.0
Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp
4500
1060 2414 2.83 1119 2685 3.15 1175 2964 3.48 1230 3250 3.81 1282 3542 4.15
4800
1082 2644 3.10 1140 2922 3.43 1195 3207 3.76 1248 3498 4.10 1299 3795 4.45
5100
1106 2894 3.39 1163 3178 3.73 1216 3470 4.07 1268 3767 4.42 1319 4071 4.77
5700
1157 3459 4.06 1211 3757 4.41 1262 4061 4.76 1312 4371 5.13 1360 4686 5.50
6000
1184 3774 4.43 1236 4080 4.79 1287 4391 5.15 1335 4707 5.52 1382 5029 5.90
6300
1212 4114 4.83 1263 4427 5.19 1312 4745 5.57 1359 5067 5.94
6600
1241 4478 5.25 1290 4798 5.63 1338 5122 6.01
6900
1270 4866 5.71
7200
———————————————
7500
———————————————
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.22.42.62.83.0
Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp
4500
1332 3841 4.50 1381 4145 4.86 1428 4456 5.23 1473 4772 5.60 1518 5095 5.98
4800
1349 4100 4.81 1397 4409 5.17 1443 4725 5.54 1488 5046 5.92
5100
1367 4380 5.14 1414 4695 5.51 1460 5016 5.88
5700
1407 5007 5.87
6000
———————————————
6300
———————————————
6600
———————————————
6900
———————————————
7200
———————————————
7500
———————————————
Bhp
Brake Horsepower
FIOP
Factory-Installed Option
Watts
Input Watts to Motor