Table 1—Physical Data (Con’t) -- Unit 577D ----A
UNIT SIZE 48090 48115 48130 60090 60115 60130
NOMINAL COOLING CAPACITY (ton) 4 4 4 5 5 5
NOMINAL HEATING CAPACITY (Btu) 90,000 115,000 130,000 90,000 115,000 130,000
SHIPPING WEIGHT (lb)
(kg)
558
253
558
253
558
253
609
276
609
276
609
276
COMPRESSORS
Quantity
2 --- Sta ge Scroll
1
REFRIGE RANT: PURON (R---410A)
Quantity (lb)
(kg)
15.3
6.9
15.3
6.9
15.3
6.9
15.8
7.2
15.8
7.2
15.8
7.2
REFRIGERANT METERING DEVICE TXV
Size 4Ton 4Ton 4Ton 5Ton 5Ton 5Ton
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
(mm)
Motor Hp (Rpm)
3300
22
559
1/4 (1100)
3300
22
559
1/4 (1100)
3300
22
559
1/4 (1100)
3300
22
559
1/3 (1110)
3300
22
559
1/3 (1110)
3300
22
559
1/3 (1110)
OUTDOOR COIL
Row s...Fins/in.
Fac e Area (sq ft)
2...21
19.4
2...21
19.4
2...21
19.4
2...21
23.3
2...21
23.3
2...21
23.3
INDOOR COIL
Row s...Fins/in.
Fac e Area (sq ft)
3...17
5.7
3...17
5.7
3...17
5.7
4...17
5.7
4...17
5.7
4...17
5.7
INDOOR FAN
Nominal Airflow (Cfm)
Comfort Variable based on Comfort Roll back (see User Interface instructions for more information).
Efficiency 1400 1400 1400 1750 1750 1750
Max 1600 1600 1600 2000 2000 2000
Furnace (gas ht.) airflow---Low Stage 815 1215 1255 845 1215 1255
Furnace (gas ht.) airflow---High Stage 1385 1885 1875 1300 1910 1920
Size (in.)
(mm)
11x10
279x254
11x10
279x254
11x10
279x254
11x10
279x254
11x10
279x254
11x10
279x254
Motor HP (RPM) 3/4 3/4 3/4 1 1 1
FURNACE SECTION*
Burner Orifice No. (Qty...Drill Size)
Natural Gas (Factory Installed)
Propane Gas
3...38
3...53
3...33
3...51
3...31
3...49
3...38
3...53
3...33
3...51
3...31
3...49
HIGH---PRESSURE SWITCH (psig)
Cut --- out
Reset (Auto)
670 ± 10
470 ± 25
HIGH---PRESSURE SWITCH 2 (psig)
(Compressor Solenoid)
Cut --- out
Reset (Auto)
565 ± 15
455 ± 15
LOS S --- OF --- CHA RGE /
LOW---PRESSURE SWITCH
(Liquid Line) (psig)
Cut --- out
Reset (auto )
23 ± 5
55
± 5
RETURN---AIR FILTERS Throwaway†(in.)
(mm)
24x36x1
610x914x25
*Based on altitude of 0 to 2000 ft ( 0 to 610 m).
{Recommended filter sizes for field---installed air filter grilles mounted on the wall or ceiling of the conditioned structure. Required filter sizes shown are based on
the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway
type or 450 ft/minute fo r high---capacity type. Ai r fi lter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.
577D-- -- A