Bacharach ADM800 Smoke Alarm User Manual


 
32 Instruction 3015-4275
ADM800 - System Programming
Setup Parameters
Before working with the AGM300 network, several global parameters must be defined. Most of these are
entered in the ADM Setup Screens or via the PC software. Parameters must also be defined for each
AGM300 monitor connected to the network. These settings serve to identify each monitor and define how they
operate. These are entered in the AGM Setup Screens. Finally, parameters must be defined for each
individual monitoring zone. These are entered in the Zone Setup Screens.
Password Protection
The ADM800 can be password protected to prevent the unauthorized editing of setup parameters. When
password protection is enabled, an operator may still navigate between screens to observe settings or monitor
network status. The password can be alphanumeric.
The unit is shipped with password protection OFF. Entering a password in ADM Setup Screen #1 enables
password protection. Once protection is enabled the user will be prompted to enter the password when they
first attempt to edit a setup parameter.
To enter a password:
1. From the top level System Screen press the ADM SETUP key to go to ADM Setup Screen #1.
2. From ADM Setup Screen #1, press the PASSWORD key.
3. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual characters.
4. Press ENTER to accept the new password or QUIT to revert to the previous setting.
After entering the password, a 30 minute time period will be allowed for entries; after which, the user will again
be prompted to re-enter the password.
IMPORTANT: Please make note and save your password.
ADM Setup Screen #1
Password