Bacharach ADM800 Smoke Alarm User Manual


 
Instruction 3015-4275 27
Changing Terminator Switch Settings
The terminator switch for the RS-485 “TO MONITORS” connector is shipped from the factory in the terminated
or “IN” position. This is the correct setting if the ADM800 is connected to only one AGM300, or if it is the last
device on a network chain. If the ADM800 is being installed in the middle of a network, the terminator must be
moved to the “OUT” position. Refer to Multiple AGM's on Page
12.
The terminator switch for the RS-485 “TO HOST” connector is shipped from the factory in the terminated or “IN”
position. This is the correct setting if the ADM800 is the last device on the network chain. If other devices are
daisy chained through the ADM800, the terminator must be moved to the “OUT” position. Refer to Connecting
to a Building Management System on Page
12.
Locate each terminator switch and determine its position. If it needs to be moved, carefully slide the switch to
the proper position.
RS-485
TO MONITOR
Connector
RS-485
TO HOST
Connector
Terminator for RS-485
TO HOST
Connector
OUT
IN
Terminator for RS-485
TO MONITOR
Connector
OUT
IN