Sanyo CH4272R H/P Air Conditioner User Manual


 
81
RC
(WL)
Sliding switch 1
Wireless remote controller transmitter
Verify that sliding switch 1 is in the “K” position.
<For 3072R, 3672R>
S: Flap model (4-direction, ceiling suspended)
K: Swing-only model (wall-mounted), settings completed
N: No-flap model (built-in)
SKN
Verify that sliding switch 1 is in the “S” position.
<For 2672R>
SKN
Sliding switch 2
SENSOR button
RESET button
Set sliding switch 2 to the correct setting for these models.
A: Heat pump model
(H: Heat pump, no auto heating/cooling)
C: Cooling-only model
AHC AHC
7-19. Test Run Procedure
<RCS-SH1UA>
7-20. Check Items Before the Test Run
Wall-mounted Type
(K Type)
Check the “Check Items Before the Test Run.”
Set the indoor unit controller to “TEST.”
Return the indoor unit controller to
“NORM.” (Item 7-21-3)
NO
Is operation
possible?
Verify the combination (wiring) of indoor and
outdoor units.
Check using the self-diagnostics
function table. (Refer to 11-7)
Correct any locations that require
correction.
YES
Note: Check the indoor-side drainage.
(Item 7-20)
(Item 7-21-3)
(1)
Turn ON the remote power switch at least 5 hours before the test run in order to charge the crank-case heater.
(If the outdoor unit is an inverter unit, turn ON the power 12 hours in advance.)
(2) Fully open the service valves on the gas-tube and liquid-tube sides.
(3)
Set the sliding switches on the inside of the wireless remote controller cover to the correct settings for that model.
After changing the settings, press the RESET button.