Rinnai Corporation Hydronic Furnace (37AHB) Manual
NOTES:
1. EWT - Entering Water Temperature (F).
2. CFM - Airflow in (Cubic Feet per Minute).
3. Legs - 3 inch diameter flexible ducts to diffusers.
4. 1 MBH = 1000 BTU/H.
5. Shaded box represents rating point; refer to wiring diagram for factory set speed taps.
6. Number of 3” diameter legs specified in table above is for rating point only (i.e. at External Static Pressure of 0.5
in. wc. and speed TAP3, TAP1, TAP2 , TAP2 for AHB45, AHB60, AHB75, AHB90 respectively). Final leg count is
to be determined by the installing contractor and is to be based on the following formula:
NUMBER OF LEGS = TOTAL AVAILABLE CFM
(AT THE SPECIFIC ESP)
/ DESIRED CFM per LEG
(40, 50, or 60 CFM)
Example: Given the design point for AHB045 of 0.8 ESP, Low fan speed (Tap5). From table 5.0, available CFM is
569 and the desired CFM per leg is 50 CFM. Therefore, Number of Legs = 569/50 = 11.38 rounded down to 11.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1343 1318 1296 1270 1248 1225 1197 1168 1109 1025 889
120 43.6 42.8 42.1 41.2 40.5 39.8 38.8 37.9 36.0 33.3 28.8
130 50.9 49.9 49.1 48.1 47.3 46.4 45.3 44.3 42.0 38.8 33.7
140 59.5 58.4 57.4 56.3 55.3 54.3 53.1 51.8 49.2 45.4 39.4
150 68.6 67.4 66.2 64.9 63.8 62.6 61.2 59.7 56.7 52.4 45.4
160 75.2 73.8 72.6 71.2 69.9 68.6 67.1 65.4 62.1 57.4 49.8
1148 1128 1103 1072 1045 1012 984 955 937 908 690
120 40.3 39.6 38.7 37.6 36.7 35.5 34.5 33.5 32.9 31.9 24.2
130 48.0 47.2 46.1 44.8 43.7 42.3 41.2 40.0 39.2 38.0 28.9
140 56.2 55.2 54.0 52.5 51.2 49.5 48.2 46.7 45.9 44.4 33.8
150 65.1 64.0 62.5 60.8 59.3 57.4 55.8 54.2 53.1 51.5 39.1
160 72.9 71.6 70.0 68.1 66.4 64.3 62.5 60.6 59.5 57.7 43.8
971 942 911 880 847 817 784 751 715 680 642
120
39.6 38.4 37.2 35.9 34.6 33.3 32.0 30.6 29.2 27.7 26.2
130
46.8 45.4 43.9 42.4 40.8 39.4 37.8 36.2 34.5 32.8 31.0
140
54.6 52.9 51.2 49.5 47.6 45.9 44.1 42.2 40.2 38.2 36.1
150
62.6 60.7 58.7 56.7 54.6 52.7 50.5 48.4 46.1 43.8 41.4
160
70.1 68.0 65.8 63.6 61.2 59.0 56.6 54.2 51.6 49.1 46.4
844 810 777 734 698 665 626 581 533 504 466
120
37.6 36.1 34.6 32.7 31.1 29.6 27.9 25.9 23.8 22.5 20.8
130
44.3 42.5 40.8 38.6 36.7 34.9 32.9 30.5 28.0 26.5 24.5
140
51.4 49.3 47.3 44.7 42.5 40.5 38.1 35.4 32.4 30.7 28.4
150
57.8 55.4 53.2 50.2 47.8 45.5 42.8 39.8 36.5 34.5 31.9
160
64.1 61.5 59.0 55.7 53.0 50.5 47.5 44.1 40.5 38.3 35.4
TBD
See Note 6.
AHB60 + R50LSi
AIRFLOW (CFM)
Minimum Legs @
60 CFM/Leg
Optimal Legs @
50 CFM/Leg
Maximum Legs @
40 CFM/Leg
TAP 5
(L)
1.5
NET
HEATING
CAPACITY
(MBH)
TBD
See Note 6.
TBD
See Note 6.
TAP 4
(ML)
2.0
NET
HEATING
CAPACITY
(MBH)
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
AHB60 + R50LSi
AIRFLOW (CFM)
Minimum Legs @
60 CFM/Leg
Optimal Legs @
50 CFM/Leg
Maximum Legs @
40 CFM/Leg
AHB60 + R50LSi
AIRFLOW (CFM)
Minimum Legs @
60 CFM/Leg
Optimal Legs @
50 CFM/Leg
Maximum Legs @
40 CFM/Leg
TAP 2
(MH)
2.5
NET
HEATING
CAPACITY
(MBH)
TBD
See Note 6.
TBD
See Note 6.
Minimum Legs @
60 CFM/Leg
Optimal Legs @
50 CFM/Leg
Maximum Legs @
40 CFM/Leg
TAP 1
(H)
3.0
NET
HEATING
CAPACITY
(MBH)
20 24 30
TABLE 5.24: AIR DELIVERY AND PERFORMANCE DATA (BOTTOM OR SIDE RETURN w/ FACTORY SUPPLIED FILTER)
UNIT
SIZE
ECM
SPEED
TAP
SUPPORTS
COOLING CAP.
RANGE (TONS)
EWT (
O
F)
NOMINAL
HEATING
CAPACITY
External Static Pressure (ESP) in. W.C.
Number of 3" diameter branch legs applicable to High
Velocity Systems only. Uded only if methods other than
Table 3 is used to determine duct sizes.
37AHB06012KA5 + REU-VA2019FFUD
AHB60 + R50LSi
AIRFLOW (CFM)