Rinnai 37AHB Furnace User Manual


 
Rinnai Corporation Hydronic Furnace (37AHB) Manual 35
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1343 1318 1296 1270 1248 1225 1197 1168 1109 1025 889
120 41.0 40.3 39.6 38.8 38.1 37.4 36.6 35.7 33.9 31.3 27.2
130 47.4 46.5 45.7 44.8 44.0 43.2 42.2 41.2 39.1 36.2 31.4
140 54.8 53.8 52.9 51.8 50.9 50.0 48.8 47.6 45.2 41.8 36.3
150 63.7 62.6 61.5 60.3 59.2 58.1 56.8 55.4 52.6 48.6 42.2
160 70.4 69.1 68.0 66.6 65.5 64.3 62.8 61.3 58.2 53.8 46.6
1148 1128 1103 1072 1045 1012 984 955 937 908 690
120 37.9 37.3 36.4 35.4 34.5 33.4 32.5 31.5 31.0 30.0 22.8
130 44.5 43.7 42.8 41.6 40.5 39.2 38.2 37.0 36.3 35.2 26.8
140 52.1 51.2 50.1 48.7 47.4 45.9 44.7 43.4 42.5 41.2 31.3
150 60.5 59.4 58.1 56.5 55.1 53.3 51.9 50.3 49.4 47.8 36.4
160 66.9 65.7 64.3 62.5 60.9 59.0 57.3 55.6 54.6 52.9 40.2
971 942 911 880 847 817 784 751 715 680 642
120 35.0 34.0 32.8 31.7 30.5 29.5 28.3 27.1 25.8 24.5 23.1
130 41.9 40.6 39.3 37.9 36.5 35.2 33.8 32.4 30.8 29.3 27.7
140 49.6 48.1 46.5 44.9 43.2 41.7 40.0 38.3 36.5 34.7 32.8
150 58.6 56.9 55.0 53.1 51.1 49.3 47.3 45.3 43.2 41.1 38.8
160 63.8 61.9 59.8 57.8 55.6 53.6 51.5 49.3 47.0 44.7 42.2
844 810 777 734 698 665 626 581 533 504 466
120 33.3 32.0 30.7 29.0 27.6 26.3 24.7 22.9 21.0 19.9 18.4
130 39.7 38.1 36.5 34.5 32.8 31.2 29.4 27.3 25.0 23.7 21.9
140 46.8 44.9 43.1 40.7 38.7 36.9 34.7 32.2 29.6 28.0 25.8
150 55.1 52.9 50.7 47.9 45.6 43.4 40.9 37.9 34.8 32.9 30.4
160 59.6 57.2 54.9 51.8 49.3 47.0 44.2 41.0 37.6 35.6 32.9
20 24 30
Minimum Legs @
60 CFM/Leg
Optimal Legs @
50 CFM/Leg
Maximum legs @
40 CFM/Leg
Minimum Legs @
60 CFM/Leg
20 24 30
Optimal Legs @
50 CFM/Leg
Maximum legs @
40 CFM/Leg
30
UNIT
SIZE
ECM
SPEED
TAP
SUPPORTS
COOLING CAP.
RANGE (TONS)
Number of 3" Diameter Branch Legs applicable to High
Velocity Systems Only. Used only if methods other
than Table 3 is used to determine duct sizes.
20 24 30
37AHB06012KA5 + REU-KA2530FFUD(WD)-US
AHB60 + RC80HPi(e)
AIRFLOW (CFM)
TAP 1
(H)
3.0
NET
HEATING
CAPACITY
(MBH)
AHB60 + RC80HPi(e)
AIRFLOW (CFM)
TAP 2
(MH)
2.5
NET
HEATING
CAPACITY
(MBH)
EWT (
O
F)
NOMINAL
HEATING
CAPACITY
External Static Pressure (ESP)
TABLE 5.3: AIR DELIVERY AND PERFORMANCE DATA (BOTTOM OR SIDE RETURN w/ FACTORY SUPPLIED FILTER)
NET
HEATING
CAPACITY
(MBH)
AHB60 + RC80HPi(e)
AIRFLOW (CFM)
TAP 5
(L)
1.5
NET
HEATING
CAPACITY
(MBH)
AHB60 + RC80HPi(e)
AIRFLOW (CFM)
TAP 4
(ML)
2.0
Optimal Legs @
50 CFM/Leg
Maximum legs @
40 CFM/Leg
20 24
Minimum Legs @
60 CFM/Leg
Optimal Legs @
50 CFM/Leg
Maximum legs @
40 CFM/Leg
Minimum Legs @
60 CFM/Leg
NOTES:
1. EWT - Entering Water Temperature (F).
2. CFM - Airflow in (Cubic Feet per Minute).
3. Legs - 3 inch diameter flexible ducts to diffusers.
4. 1 MBH = 1000 BTU/H.
5. Shaded box represents rating point; refer to wiring diagram for factory set speed taps.
6. Number of 3” diameter legs specified in table above is for rating point only (i.e. at External Static Pressure of 0.5
in. wc. and speed TAP3, TAP1, TAP2 , TAP2 for AHB45, AHB60, AHB75, AHB90 respectively). Final leg count is
to be determined by the installing contractor and is to be based on the following formula:
NUMBER OF LEGS = TOTAL AVAILABLE CFM
(AT THE SPECIFIC ESP)
/ DESIRED CFM per LEG
(40, 50, or 60 CFM)
Example: Given the design point for AHB045 of 0.8 ESP, Low fan speed (Tap5). From table 5.0, available CFM is
569 and the desired CFM per leg is 50 CFM. Therefore, Number of Legs = 569/50 = 11.38 rounded down to 11.
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
TBD
See Note 6.
in. W.C.