7100FP EPA Woodburning Fireplace
R
F. Mantel
A combustible mantel may be positioned no lower than 12 in.
(305 mm) above the top of the replace opening, or 60 in.
(1524 mm).
The combustible mantel may have a maximum depth of
12 in. (305 mm). Combustible trim pieces that project no
more
than 1-1/2 in. (38 mm) from the face of the replace
can be placed no closer than 6 in. (152 mm) from the top
of the replace opening. See Figure 43.1. Combustible trim
must not cover the metal surfaces of the replace. This man-
tel clearance is in accordance with Section 7-3.3.3 of ANSI/
NFPA211.
Refer to page 12 for reduced mantel heights.
Figure 43.1 Mantel Speci cations
60in.
(1524mm)
Mantel
Clearances are
from bottom of
appliance to lower
edge of mantel