For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient
location. Route 2 strand solid core millivolt wire from the gas appliance to the wall switch / millivolt thermostat.
The recommended maximum lead length depends on the wire size:
WIRE SIZE MAX. LENGTH
14 gauge 100 feet
16 gauge 60 feet
18 gauge 40 feet
DIRECT VENT MODEL GDS60: Disconnect one of the wire leads to the on/off switch then connect the wire
leads from the optional thermostat / wall switch / remote. See "WIRING DIAGRAM" section.
B-VENT MODEL GS60: Disconnect one of the wire leads to the on/off switch then connect the wire leads from
the optional thermostat / wall switch / remote / spill switch to "B" vent adaptor. See "WIRING DIAGRAM" sec-
tion.
5.6 OPTIONAL WALL SWITCH / THERMOSTAT
30.1
Installation and servicing to be done by a qualifi ed installer. Do not use open fl ame.
• Move the appliance into position and secure.
• If equipped with a fl ex connector the appliance is designed to accept a 1/2” gas supply. Without the
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off
valve to turn off the gas supply to the appliance.
• Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
• When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
• Check for gas leaks by brushing on a soap and water solution.
5.5.1
5.5.2
5.5.3
5.5.4
5.5.5
5.7 B-VENT SPECIFICS - MODEL GS60
5.7.1 CHIMNEY INSTALLATION
“A” VENT - SOLID
FUEL WOOD BURNING
CHIMNEY & VENT
CONNECTOR
(LINER NEEDED
IF INSIDE
DIAMETER IS 6”
OR LARGER)
SINGLE WALL
OR “B” VENT
MASONRY CLAY LINED
CHIMNEY + VENT
CONNECTOR
(NO NEW LINER
NEEDED IF OLD
LINER DIAMETER
IS 4-5”)
SINGLE WALL
OR “B” VENT
“B” VENT
LIQUID FUEL
GAS BURNING
CHIMNEY
A CHIMNEY VENTING THIS APPLIANCE SHALL NOT VENT ANY SOLID FUEL BURNING APPLIANCE.
!
WARNING
FIGURE 5.7.1a
FIGURE 5.7.1b
FIGURE 5.7.1c