Mitsubishi Electronics PUHY-HP-THMU-A Air Conditioner User Manual


 
15
GBDFEINLPGRRUTRCZSVSLHGPO
[Fig. 11.3.3] Combination of outdoor units and transmission booster unit
IC IC RP
Ground
TB2 TB3
M2
TB3
OC
(51)
IC IC
L6L5L3L2L1
OS
(52)
M1M2 S
TB5
M1 M2 S
TB5
ABS ABS
M1 M2
TB3
M1
M1 M2 S
TB5
M1M2 S
TB5
ME
AB
AB
L
4
r
1
r
1
L
7
ME
A Group 1 B Group 3 C Group 5 D Shielded wire E Sub remote controller
( ) Address
<Wiring Method and Address Settings>
a. Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, OC-OS and IC-IC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal
on the transmission line terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2
and terminal S on the transmission line block of the indoor unit (IC). For OC and OS, connect TB3 to TB3.
c. Connect terminals 1 (M1) and 2 (M2) on the transmission line terminal block of the indoor unit (IC) that has the most recent address within the same group to the terminal
block on the remote controller (RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit in a different refrigerant system (OC). For OC and
OS in the same refrigerant system, connect TB7 to TB7.
e. When the power supply unit is not installed on the central control transmission line, change the jumper connector on the control board from CN41 to CN40 of only one
outdoor unit in the system.
f. Connect the terminal S on the terminal block for central control (TB7) for the outdoor unit (OC) for the unit into which the jumper connector was inserted into CN40 in the
Step above to the ground terminal
in the electrical component box.
g. Set the address setting switch as follows.
*To set the outdoor unit address to 100, the outdoor address setting switch must be set to 50.
Unit Range Setting Method
Indoor unit (Main) 01 to 50 Use the most recent address within the same group of indoor units
Indoor unit (Sub) 01 to 50
Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be
in sequence with the IC (Main)
Outdoor Unit (OC, OS) 51 to 100
Set the addresses of the outdoor units in the same refrigerant system in the order of sequential number. OC and OS are
automatically identified. (*1)
M-NET R/C (Main) 101 to 150 Set at an IC (Main) address within the same group plus 100
M-NET R/C (Sub) 151 to 200 Set at an IC (Main) address within the same group plus 150
MA R/C Unnecessary address setting (Necessary main/sub setting)
h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.
i. When the centralized remote controller is connected to the system, set centralized control switches (SW2-1) on control boards in all outdoor units (OC, OS) to “ON”.
*1 OC and OS of the outdoor units in the same refrigerant system are automatically identified. They are identified as OC and OS in descending order of capacity. (If the
capacity is the same, they are identified in the ascending order of their address number.)
<Permissible Lengths>
1 M-NET Remote controller
Max length via outdoor units: L
1+L2+L3+L4 and L1+L2+L3+L5 and L1+L2+L6
=
500 m [1640 ft] (1.25 mm
2
[AWG 16] or more)
Max transmission cable length: L
1 and L3+L4 and L3+L5 and L6 and L2+L6
=
200 m [656 ft] (1.25 mm
2
[AWG 16] or more)
Remote controller cable length:r
1, r2, r3, r4
=
10 m
[32 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
If the length exceeds 10 m
[32 ft], use a 1.25 mm
2
[AWG 16] shielded wire. The length of this section (L8) should be included in the
calculation of the maximum length and overall length.
2 MA Remote controller
Max length via outdoor unit (M-NET cable): L
1+L2+L3+L4 and L1+L2+L6
=
500 m [1640 ft] (1.25 mm
2
[AWG 16]
or more)
Max transmission cable length (M-NET cable): L
1 and L3+L4 and L6 and L2+L6
=
200 m [656 ft] (1.25 mm
2
[AWG 16]
or more)
Remote controller cable length:c
1+c2 and c1+c2+c3+c4
=
200 m [656 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
3 Transmission booster
Max transmission cable length (M-NET cable):1 L
1+L2+L3+L5+L6
=
200 m [656 ft] (1.25 mm
2
[AWG 16])
2 L
1+L2+L3+L5+L7
=
200 m [656 ft] (1.25 mm
2
[AWG 16])
3 L
1+L2+L4
=
200 m [656 ft] (1.25 mm
2
[AWG 16])
4 L
6+L5+L3+L4, L4+L3+L5+L7
=
200 m [656 ft] (1.25 mm
2
[AWG 16])