Mitsubishi Electronics MXZ-8B48NA Air Conditioner User Manual


 
74
SW2 setting
Display detail
Explanation for display
Unit
1
ON
23456
1
ON
23456
Indoor pipe temperature / Liquid
TH2
Indoor-B
– 35~88 (°C)
– 31~190 (°F)w
Indoor pipe temperature / Liquid
TH2
Indoor-C
– 39~88 (°C)
– 38~190 (°F)w
°C
°F(w)
°C
°F(w)
– 39~88 (°C), – 38~190 (°F)
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
1
ON
23456
1
ON
23456
LEV-2 opening pulse
0~500
– 35~88 (°C), – 31~190 (°F)
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
1
ON
23456
1
ON
23456
Indoor pipe temperature / Liquid
TH2
Indoor-D
– 39~88 (°C)
– 38~190 (°F)w
– 39~88 (°C), – 38~190 (°F)
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
°C
°F(w)
– 39~88 (°C), – 38~190 (°F)
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
0~500
°C
°F(w)
Pulse
Pulse
0~500
Indoor pipe temperature / Liquid
TH2
Indoor-E
– 39~88 (°C)
– 38~190 (°F)w
LEV-1 opening pulse
0~500
1
ON
23456
Pulse
1
ON
23456
1
ON
23456
LEV-3 opening pulse
0~500
LEV-4 opening pulse
0~500
0~500
Pulse
Pulse
0~500
LEV-5 opening pulse
0~500
0~500
1
ON
23456
Outdoor pipe temperature / 2-phase
(TH6)
– 39~88 (°C)
– 38~190 (°F)w
°C
°F(w)
– 39~88 (°C), – 38~190 (°F)
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
°C
°F(w)
– 39~88 (°C), – 38~190 (°F)
(When the temperature is 0: or less, “–” and
temperature are displayed by turns.)
1
ON
23456
Outdoor outside temperature (TH7)
– 39~88 (°C)
– 38~190 (°F)w
w SW1-8 : OFF (Unit: °C), SW1-8 : ON (Unit: °F)