Mitsubishi Electronics MXZ-8B48NA Air Conditioner User Manual


 
46
Thermistors
Open detection Short detection
Symbol
Name
TH3
TH7
TH8
Branch box unit
TH-A~E
(Room A-E)
– 40[– 40°F] or below
– 40[– 40°F] or below
– 35[– 30°F] or below
90[194°F] or above
90[194°F] or above
170[338°F] or above
– 40[– 40°F] or below 90[194°F] or above
Thermistor <Outdoor pipe>
Thermistor
(Gas pipe temperature detection)
Thermistor <Outdoor>
Internal thermistor <Heatsink>
Error Code
Abnormal point and detection method
Case
Judgment and action
U4
(TH3:5105)
(TH7:5106)
(TH8:5110)
(63HS:5201)
TH-A~E
:5131
(1) Open/short circuit in the outdoor unit
thermistors (TH3, TH7, and TH8) and
branch box’s thermistors(TH-A~E)
Abnormal if open or short circuit is detected
while the compressor is operating.
Open detection of thermistors TH3 is inopera-
tive for 10 seconds to 10 minutes after com-
pressor starting and 10 minutes after recov-
ery from defrosting and during defrosting.
WCheck which unit has abnormality in its
thermistor by switching the mode of SW2.
(Refer to 8-8.)
Open/short circuit in the branch box ther-
mistor. (TH-A–TH-E)
1One or more connectors on
outdoor controller circuit board
(TH3, TH7 and TH8) and branch
box controller board (TH-A~E)
have contact failure or discon-
nection.
2Defective thermistor
3Outdoor controller circuit board
is defective.
1 Check the connector’s contact and the electric
wires of thermistor.
2Check the resistance value of thermistors or
the temperatures by referring to the section of
“Monitoring function for outdoor unit”.
(Convert modes by SW2.)
3Replace the whole outdoor controller board.
U5
(4230)
Abnormal temperature of heatsink
Abnormal if heatsink thermistor(TH8)
detects temperature indicated 93 °C [200 °F]
1
The outdoor fan motor is locked
.
2 Failure of outdoor fan motor
3 Air flow path is clogged.
4 Rise of ambient temperature
5 Defective thermistor
6 Defective input circuit of
outdoor power circuit board
7 Failure of outdoor fan drive
circuit
12 Check outdoor fan.
3 Check air flow path for cooling.
4 Check if there is something which causes
temperature rise around outdoor unit.
(Upper limit of ambient temperature is 46:
[115°F].)
Turn off power, and on again to check if U5
is displayed within 30 minutes.
If U4 is displayed instead of U5, follow the
action to be taken for U4.
5 Check resistance value of thermistor (TH8)
or temperature by microprocessor.
(Thermistor/TH8: Refer to 8-6.)
(SW2 on A-Control Service Tool: Refer to 8-8.)
6 Replace outdoor power circuit board.
7 Replace outdoor controller circuit board.
U6
(4250)
Abnormality of power module
Check abnormality by driving power module
in case overcurrent is detected.
(UF or UP error condition)
1 Outdoor stop valve is closed.
2 Decrease of power supply voltage
3 Looseness, disconnection or
converse of compressor wiring
connection
4 Defective compressor
5 Defective outdoor power circuit
board
1 Open stop valve.
2 Check facility of power supply.
3 Correct the wiring (U·V·W phase) to
compressor. Refer to 8-7.
4 Check compressor referring to 8-6.
5 Replace outdoor power circuit board.
()
(2) High-Pressure sensor (63HS) abnormality
1When detected pressure in high-pressure
sensor is 1MPa [145PSIG] or less during
the operation, the compressor stops and
restarts operation in 3 minutes.
2When the detected pressure is 1MPa
[145PSIG] or less at just before of restart-
ing, the compressor stops abnormally. In
this time, <U4> is displayed.
3For 3 minutes after the compressor stops,
the unit delays abnormal stop. Then, the
outdoor unit address No. and check delay
code <U4> blinks alternately on the 7
SEG digital display.
4For 3 minutes after starting compressor,
for defrosting or for 3 minutes after recov-
ery from defrosting, abnormality is not
determined as abnormality.
1 Check the high-pressure sensor.
2 Check the internal pressure.
3 Check the high-pressure sensor.
4 Check the outdoor controller board
1High-pressure sensor failure
2Internal pressure decrease by
gas leakage
3Connector contact failure dis-
connection
4Controller board input circuit
failure