16 Installation (for qualified installers only)
Travis Industries 100-01159 4040621
Approved Venting Configurations with a Horizontal Termination
and Three 90° Elbows (all vertical)
If using a Snorkel Termination (14 or 36) add the snorkel height to the vertical height (snorkel
terminations are used primarily for basement installations).
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position.
5 feet
10' (min)
15 feet
21' (max)
0 feet
5 feet
0 feet
0 feet
5 feet
10' (min)
15 feet
Restrictor
Position # 5
NOTE:
Restrictor positions are based
upon lab tests. The ideal restrictor
position may vary slightly,
especially when the termination is
near a demarkation line.
Restrictor
Position # 1
10 feet
15 feet
20 feet
24 ' (max)
0 feet
5 feet
10 feet
15 feet
20 feet
24 ' (max)
21' (max)
NOTE:
Horizontal sections require a 1/4"
rise every 12" of travel.
This is a horizontal elbow -
NOT ALLOWED FOR THIS
VENT CONFIGURATION
These are
vertical elbows.