Liebert AC4 Home Security System User Manual


 
System and Control Options
33
7.6 Setup System - Setup Outputs
The AC4 has four outputs that may be configured individually. These outputs correspond to the four
numbered inputs. For example, Device_1 is the unit connected to Input 1 and to Output 1.
The output name is the same as the input name, as described in 7.3.1 -
Change Label (Name of Input).
To configure an output:
Log In and Choose Setup System
From the Main Menu, use the arrows
↑↓ to choose System and
Control, then press Enter (see 7.1 - Login for help).
Enter your password at the Login screen.
From the System and Control Menu, use the arrows
↑↓ to choose
Setup System, then press Enter .
Select an Output to Configure
From the Setup System Menu, shown at right, use the arrows
↑↓ to
choose Setup Outputs and press Enter .
From the Select Output Menu, choose an output—for example,
Device_1—and press Enter .
Table 17 shows digital output features and their default settings: you
may define an output as normally open or normally closed, set the device’s mode—operating, standby
or not used—and specify whether to disable the device when an alarm occurs.
Use the steps following Table 17 to change the default settings for any digital output.
7.6.1 Define Output as Normally Open or Normally Closed
Each output may be set up as Normally Open (NO) or Normally Closed
(NC). The default setting for all output points is NO (Normally Open).
From the Setup Outputs Menu, shown at right, use the arrows
↑↓
to
choose Norm Open/Close and press Enter .
To change the normal state for this output, use the arrows
↑↓ to
choose the state:
NO (Normally Open)
NC (Normally Closed)
Press Enter .
Table 17 Default settings - digital outputs
Feature Default Other Options
NORM OPEN/CLOSE NO (Normally open) NC (Normally closed)
MODE
Outputs 1-3:
Output 4:
OP (Operating)
ST (Standby)
OP (Operating)
ST (Standby)
NU (Not Used)
IN ALARM E (Enable) D (Disable)
Setup System Menu
SETUP INPUTS
SETUP COMMON ALARM
SETUP ZONES
↑↓=NEXT =SELECT
> SETUP OUTPUTS
SETUP SYSTEM INFO
SETUP OPERATION
Select Output Menu
SELECT OUTPUT
> DEVICE_1 NO-OP-E
DEVICE_2 NO-ST-E
↑↓=NEXT =SELECT
DEVICE_3 NO-NU-D
DEVICE_4 NO-NU-D
Setup Outputs Menu
SETUP DEVICE_1
> NORM OPEN/CLOSE: NO
MODE: OPERATING
↑↓=NEXT =SELECT
IN ALARM: ENABLE
Change State
SET TO NORMAL OPEN
OR NORMAL CLOSE? NO
↑↓=NO/NC =END