Lenox ML180UHE Furnace User Manual


 
Page 10
Return Air −− Upflow Applications
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
NOTE −
60C and 60D units that require air volumes over 1800
cfm (850 L/s) must have one of the following:
1 − Single side return air with transition to accommodate 20
x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. (Re-
quired to maintain proper air velocity.) See figure 9.
2 − Single side return air with optional return airbase. See fig-
ure 10.
3 − Bottom return air.
4 − Return air from both sides.
5 − Bottom and one side return air.
Refer to Engineering Handbook for additional information.
FIGURE 9
Return Air
Plenum
Transition
20” X 25” X 1”
(508mm X 635mm X 25mm)
Cleanable Filter
AIR FLOW
Single Side Return Air
(with transition and filter)
Optional Return Air Base
(Upflow Applications Only −− For use with A, B, C and D cabinets)
FIGURE 10
NOTE− Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches 356 mm) is preferred.
FURNACE
FRONT
AIR FLOW
141/2 (368) A Width (65W75)
171/2 (446) B Width (50W98)
21 (533) C Width (50W99)
241/2 (622) D Width (51W00)
1
Unit side return air
Opening
SIDE VIEW
31/4
(83)
1
23 (584)
Overall
(Maximum)
(584)
23
3/4
(19)
1
227/16
(570)
Overall
(Maximum
)
SIDE RETURN
AIR OPENINGS
(Either Side)
55/8
(143)
1
Minimum
11 (279)
2
Maximum
14 (356)
(683)
267/8
71/4
(184)
IF BASE
IS USED
WITHOUT
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
INDOOR AIR
QUALITY
CABINET
(PCO, Filter
Cabinet, etc.)
AIR BASE
OPTIONAL
RETURN