Lennox International Inc. Dave Lennox Signature Collection XP17 System HEAT PUMPS Heat Pump User Manual


 
Page 37
XP17 SERIES
Y1 DEMAND
HIGH
PRESSURE
SWITCH (S4)
COMPRESSOR
CONTACTOR
ENERGIZED
HIGH
PRESSURE
SWITCH (S4)
COMPRESSOR
CONTACTOR
DE−ENERGIZED
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
INCREMENT
5−STRIKE
COUNTER
1
LED ALERT
CODE / OR
MODERATE
ALERT 412
DISPLAYED
ANTI−SHORT
CYCLE TIMER
ENDS
COMPRESSOR
CONTACTOR
ENERGIZED
HIGH
PRESSURE
SWITCH (S4)
WAITING FOR
PRESSURE
SWITCH TO
CLOSE
5−STRIKE
COUNTER
REACHES 5
WITHIN A SINGLE
Y1 DEMAND
HIGH
PRESSURE
SWITCH (S4)
LOCKOUT
LED ALERT
CODE / OR
CRITICAL
ALERT 413
CLEARED
SERVICE
REQUIRED
2
LED ALERT
CODE / OR
MODERATE
ALERT 412
DISPLAYED
SERVICE
REQUIRED
2
NORMAL
OPERATION
CLOSED
CLOSED
OPEN
OPEN
1
If 5−strike counter has four or less strikes when Y1 demand is terminated
or satisfied, the strike counter will reset to zero. In a icomfort Touch
®
thermostat enabled setup, the thermostat will terminate demand when the
compressor contactor is de−energized. If demand is satisfied when alarm
is not active, the 5−strike counter will reset.
2
Lockouts can be reset by either cycling power off to the heat pump con-
trol’s (A175) R terminal, or placing a jumper on the field test pins (E33) be-
tween 1 to 2 seconds.
OPEN
CLOSED
CLOSED
Figure 29. High Pressure Switch (S4) Sequence of Operation