HP (Hewlett-Packard) 403349-003 Fan User Manual


 
Specifications 142
Specifications
MCS specifications
Item Specification
Voltage 208–240 VAC +/- 10%, 50–60 Hz
Maximum Height
(including the rack)
200 cm (78.7 in)
Maximum Width
(including the rack)
90.9 cm (35.8 in) maximum
Maximum Depth
(including the rack and
rack handle)
127 cm (50 in)
Maximum Shipping
Height (on skid)
224.8 cm (88.5 in)
Maximum Shipping
Width (on skid)
122 cm (48 in)
Maximum Shipping
Depth (on skid)
177.8 cm (70 in)
Maximum Depth with
Rear Extension Kit
installed
142.5 cm (56.1 in)
Net Weight (including
the empty rack)
540 kg (1190 lb)
Shipping Weight (gross
with packaging)
621.4 kg (1370 lb)
Effective cooling with
75 l/min (20 gal/min)
water supply at 7°C,
cold air at 25°C
35 kW
Rated current maximum 208 VAC–15 Amps
Cooling medium water
Minimum
recommended water
inlet temperature
7ºC (45ºF)
Permissible operating
pressure pmax
100 psi