F. Prefabricated Metal Chimney
E. Metal Heat Circulating Masonry
Thechimneycanbeneworexisting,masonryorprefabricated
andmustmeetthefollowingminimumrequirements:
•Mustbeminimum6inch(152mm)insidediameterof
hightemperaturechimneylistedtoUL103HT(2100
o
F)
orULCS628.
•Mustusecomponentsrequiredbythemanufacturerfor
installation.
•Mustmaintainclearancesrequiredbythemanufacturer
forinstallation.
•Refertomanufacturersinstructionsforinstallation
•This insert is listed to UL 1482 Standard and is
approved for installation into listed factory-built solid
fuel
replaceslistedtoUL127conformingtothefollow-
ingspecicationsandinstructions:
•The original factory-built clearance replace chimney
capmust bere-installedafterinstalling theapproved
chimney linermeeting typeUL 103HTrequirements
(2100°F)perUL1777.
•The linermust besecurelyattached tothe insertue
collarandthechimneytop.
•The air ow of the factory-built solid fuel replace
systemmustnotbealtered.Theuelinertopsupport
attachmentmustnotreducetheairowfortheexisting
air-cooledchimneysystem.
•Nodilutionairisallowedtoenterthechimney.
1.Securethereplacedamperintheopenposition.
Ifthiscannotbeaccomplished,itwillbenecessary
toremovethedamper.
2.Sealdamperareaofchimney aroundchimney
connectorwithahightemperaturesealantorseal
insertagainstthefaceofthereplace.
3.Bothmethodsmustberemovableandreplaceable
forcleaningandre-installation.
ThisinsertconformswiththesafetystandardUL-1482and
ULCS628(Canada)inallrespectsandisapprovedtoUL&
ULCsafetystandardsforinstallationandusewithinare-
placewithmasonrychimney,inaccordancewithNFPA211,
andCAN/CSA-B365-01.
FireRisk.
Whenliningair-cooledfactory-builtchimneys:.
• RunchimneylinerapprovedtoUL1777Type
HTrequirements(2100degreesF)
• Re-installoriginalfactorybuiltchimneycap
ONLY
• DONOTblockcoolingairopeningsinchimney
• Blockingcoolingairwilloverheatthechimney
WARNING
NOTICE:InCanadawhenusingafactory-builtchimneyitmust
besafetylisted, Type UL103 HT (2100
o
F) [1149
o
C] CLASS
“A” orconformingtoCAN/ULC-S629M, STANDARD FOR
650
o
C FACTORY-BUILT CHIMNEYS.
NOTE: Refer to chimney liner manufacturer for recom-
mendations on supporting the liner. Installation into
replaces without a permit will void the listing.
WARNING! Risk of Fire!
Followventingmanufacturer’s clearancesand
instructionswheninstallingventingsystem.
To maintain the functionality of the replace’s chimney
system you may use a Simpson Dura-Vent DuraLiner
SlipHanger,Part#4671,andattachtothebottomofthe
replacechimneycaptosupporttheliner.Youhavetwo
optionstocompletingtheinstallation.
Option one - Not required to use liner cap:
Re-attachtheexistingtopofthechimneycap.
Option two - Using liner cap:
Re-attachtheexistingtopofthechimneycapandinstalla
newstormcollarandanewlinercap.
*Youwillneedtoaddadditionalclearancestothese
dimensionsforyourspecicinstallation.Alsoallowsuf-
cientclearanceifyouareinstallinganoutsideairkit.
Minimum Width of Cavity Opening - Front
241/2* 622*
Minimum Width of Cavity Opening - Rear
241/2* 622*
Minimum Height
21-1/2* 546*
Minimum Depth from Front to Rear
16* 467*
Inches Millimeters