Heat & Glo LifeStyle 550TRSI-AUF Indoor Fireplace User Manual


 
Heat & Glo • 550TRSI-AUF, 550TRSILP-AUF • 2079-980 Rev. N • 5/12
30
Top Vent - Vertical Termination
This model is approved to use DVP-Series ue pipe com-
ponents. A DVP-TVHW vertical Termination Cap must be
used to terminate ue systems in a vertical position.
Approved ue system components are labeled for identi-
cation. NO OTHER FLUE SYSTEMS OR COMPONENTS
MAY BE USED. Detailed installation instructions are in-
cluded with each ue termination kit and should be used
in conjunction with this manual.
WARNING! Risk of Fire! This gas appliance and ue
assembly must be ued directly to the outside and must
never be attached to a chimney serving a separate solid
fuel burning appliance. Each gas appliance must use a
separate ue system-common ue systems are prohibited.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specied in
this manual. Overlapping material could ignite and will in-
terfere with proper operation of doors and louvers.
Horizontal sections 3 in. (76 mm) from the top of the
pipe.
Horizontal sections 2-1/2 in. (64 mm) at wall shield
restops.
Horizontal sections 1 in. (25 mm) from sides and bottom
of the pipe.
Vertical sections 1 in. (25 mm) on all sides of pipe.
Failure to keep insulation or other material away from vent
pipe may cause over heating and re.
For alternative installations, other than depicted, contact
your dealer for further information.
Figure 7.8
Figure 7.7
V
MAX. RUN
36 ft.
(10.97 m)
Straight Up Vertical Flue System
Figure 7.7 shows straight up vertical ue system approved
for use on this model.
If the heater installation requires a vertical ue
exceeding 14-3/4 ft. (4.5 m) above the unit
with no horizontal ue or elbows a vertical ue
restrictor must be installed (see Figure 7.7).
CAP
V
1
RESTRICTOR
PLATE
MODEL FLUE TERMINATION APPROVALS
550TRSI-AUF
550TRSILP-AUF
SLP-TVHW, DVP-TVHW