Harman Stove Company P35I Indoor Fireplace User Manual


 
11
Save These Instructions 3-90-775 Pellets or Corn/Pellet Mixture Only


When installing the P35i Insert into a factory built
wood burning replace, several things need to be taken
into consideration.
The size of the replace opening. Will the unit t into
the opening? Some of the factory built replaces have
metal smoke shields inside the top that can be removed
to gain height. Keep in mind that anything removed
from the factory built replace must be attached to the
replace with a metal wire. Floor protection guidelines,
as listed previously, must also be followed.
The manufactured replace may not be altered be-
yond the exceptions listed below. Never remove masonry
bricks or mortar from an existing replace.
The following modications are permissible:
• Removal of the damper or lock in open position
• Removal of smoke shelf or bafe
• Removal of andirons or ember catchers
• Removal of log grate
• Removal of view screen or curtain
• Removal of doors
• External trim pieces, that do not affect the operation
of the replace, may be removed providing they can
be stored on or within the replace for reassembly if
the insert is removed.
• If the hearth extension is lower than the replace
opening, the portion of the insert extending onto the
hearth must be supported.
• Final approval of this type of installation is contingent
upon the authority having jurisdiction.
Note: If the Harman P35i Insert is installed into a factory built wood burning replace, this
label (Harman part # 3-90-00675) MUST be attached to the altered replace.
The factory built chimney must be listed per UL 127 (US)
and meet type HT requirements of UL 103 (US). Factory
Built replace chimneys tested to UL 127-98 may be, at the
replace manufacturers option, tested to the same criteria
as UL 103HT requirements. If the chimney is not listed as
meeting HT requirements, or if the factory built replace was
tested prior to 1998, a full height listed chimney liner must
be installed from the appliance ue collar to the chimney top.
Liner must meet high temperature (2100 F) per UL1777 (US).
The liner must be securely attached to both the ue collar
and the chimney cap. To prevent room air passage to the
chimney cavity of the replace, seal the damper area around
the chimney liner with berglass batting.
Hearth must be constructed to
the proper height and finished
with a non-combustible
material.



















