Envision Peripherals IM1609 08 Heat Pump User Manual


 
19
ENVISION CONSOLE INSTALLATION MANUAL
Fan Performance Data
Model
CFM
Low Speed High Speed
09 300 350
12 300 350
15 450 500
18 450 500
Factory settings are in Bold
Air ow values are with dry coil and standard lter.
For wet coil performance rst calculate the face velocity of the air coil
(Face Velocity [fpm] = Airow [cfm] / Face Area [sq ft]). Then for
velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300
fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.
Unit Electrical Data
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC RLA LRA
09
208-230/60/1 197/253 6.4 4.1 21.0 0.50 4.6 5.6 10
265/60/1* 238/292 na 4.3 22.0 0.50 4.8 5.9 10
12
208-230/60/1 197/253 7.7 4.9 25.0 0.50 5.4 6.7 10
265/60/1* 238/292 na 5.3 22.0 0.50 5.8 7.1 10
15
208-230/60/1 197/253 9.2 5.9 29.0 0.69 6.6 8.1 10
265/60/1* 238/292 na 5.6 28.0 0.65 6.3 7.7 10
18
208-230/60/1 197/253 10.4 6.7 33.5 0.69 7.3 9.0 15
265/60/1* 238/292 na 7.3 28.0 0.65 8.0 9.8 15
HACR circuit breaker in USA only
* RLA determine per UL1995 test procedure and not from compressor rating.
4/8/08