Enviro C-10794 Indoor Fireplace User Manual


 
27
Initial Installation
QUALIFIED INSTALLERS ONLY
INSTALLATION OF TOP VENTED; HORIZONTAL TERMINATION:
Siding
Exterior wall
Drywall
Vent pipe
Inside
finished collar
Wall thimble
Termination
Figure 37: Installation for Top
Vented; Horizontal Termination.
INSTALLATION OF TOP VENTED; VERTICAL TERMINATION:
Vent cap
Roof flashing
Roof
truss
Flue pipe
Insulation
gaurd
Ceiling
support
Inside
finished collar
Figure 38: Installation for Top Vented;
Vertical Termination.
This is the most common type of installation style.
Set the unit in place.
Install a minimum 24” (61 cm) vertical chimney.
Install a 90° elbow, and mark the exterior wall where the vent would
pass through.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain clearances
to combustibles around vent pipe. Frame hole if as shown in Figure
17.
Install wall thimble.
Install interior nished collar
Install the vent section through the wall and then install the vent
termination.
Seal around the termination using a non hardening mastic.
CORNER INSTALLATION:
This type of installation can be used in a corner installation. If a
90° elbow is used in the horizontal plane, 36” (91.4 cm) must be
subtracted from the allowable horizontal run shown in Figure 12.
Place the unit in place.
Drop a plumb bob from the ceiling to the center point of the
ue outlet.
Cut a 10” (25.4 cm) hole in the ceiling and the roof. Refer to
Figure 23.
Install the ceiling support and insulation guard.
Install the roof ashing. Ensure that the roof ashing is
installed under the roong material so that a watertight seal
is created.
Install the ue pipe from the top of the unit through the
roof.
Ensure that all ue pipe and unit maintain required clearances
to combustibles.
CORNER INSTALLATION:
This type of installation can be used in a corner installation.
If a 90° elbow is used in the horizontal plane, 36” (91.4 cm)
must be subtracted from the allowable horizontal run shown
in Figure 12.