Enviro C-10794 Indoor Fireplace User Manual


 
Firebox Top
Flue Collar
Adapter
Undo four "
screws that
hold flue collar
elbow to unit.
Figure 34: Step 3 of Converting Top Vented into
Rear Vented.
Figure 35: Step 4 of Converting Top
Vented into Rear Vented.
INSTALLATION OF REAR VENTED APPLIANCE:
Siding
Exterior wall
Drywall
Vent pipe
Inside finished collar
Wall thimble
Minimum vent terminal 36"
(91.4cm) high snorkel kit.
Figure 36: Installation for Rear Vented;
30,000 Btu/hr.
26
Initial Installation
QUALIFIED INSTALLERS ONLY
CONVERTING TOP VENTED INTO REAR VENTED:
This unit has been shipped as a 30,000 Btu/hr top-vented freestanding unit. This unit can be converted
to a rear vented unit with a 36” (915 mm) snorkel for some installation applications.To convert this unit
to a rear vented model you must remove the ue pipe adapter and turn to the rear vent position. See
sections INITIAL INSTALLATION - INSTALLATION OF REAR VENTED APPLIANCE.
1. Carefully remove the trivet and the stovetop. Place on a
soft surface as not to damage the porcelain nishes.
2. Remove the four (4)
” screws that hold
the ue collar elbow
to the unit body (see
Figure 34).
3. Carefully remove the
elbow being sure
not to damage the
gasket that is glued
to the ue collar
elbow, it seals the
ue to the rebox.
4. Turn the elbow to the rear vent position and re-fasten with the
screws removed in step 2 (see Figure 35).
Place the unit into position.
Attach a small section of pipe on the unit and mark exterior wall
where vent would pass through the wall.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain
clearances to combustibles. Frame hole as shown in Figure 17.
Install a wall thimble.
Install interior nished collar.
Install the vent section through the wall.
THIS UNIT MUST BE VENTED WITH A 36” (91 cm) SNORKEL KIT
IF UNIT IS RATED FOR 30,000 Btu/hr NG and 26,000 Btu/hr LP.
Seal around the vent terminal to the structure using a non
hardening mastic.