Emerson 3-9000-771A Carbon Monoxide Alarm User Manual


 
Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual Section 4: Configuring a 3818 LNG Meter
3-9000-771 Rev A May 2012
Using AMS Device Manager to configure the meter 69
AMS Device Manager - Manual Setup
Use the
Manual Setup wizard to configure the meter’s parameters. See Figure 4-4 and Figure 4-5
and from the AMS Device Manager Configure menu click
Manual Setup.
Figure 4-10 AMS Device Manager - Configure Manual Setup
Procedure
1. If installed, remove security wires from the endcap and the Bracket/Cover hex head
bolts that secures the Base Enclosure.
1. Disable the Write Protect switch in the CPU Module to write any of the following
configuration parameters to your meter.
2. Click the
Device Variables Mapping tab. The Primary and Secondary variables are read
only and are configured for Uncorrected Flow Rate. The Third and Fourth variable
configuration choices include Pressure and Temperature.
3. Click the
Units tab (see AMS Device Manager - Guided Setup, Step 1).
4. Click the Analog Output 1 (HART) tab (see AMS Device Manager - Guided Setup, Step
2a.).
5. Click the
Analog Output 2 tab. Follow the configuration instructions in the AMS Device
Manager - Guided Setup, Step 2b. The read only Secondary variable Content,
Uncorrected Flow Rate, displays. Use the drop-down arrow and select the (flow)
Direction - Forward or Reverse. Enter a Lower and Upper Range limit. Set the Alarm
Action parameters. Click
Apply, after you enter the data to write the parameters to the
meter.